Tiny Addressable Serial Converter
ICP DAS CO., LTD.
User Manual, Ver. 1.3, Apr. 2018, Page: 32
Item Descriptions:
Item
Description
Default
Baud Rate (bps)
Sets the Baud Rate for the COM ports.
115200
Data Size (bits)
Sets the Data Size for the COM ports.
8
Parity
Sets the Parity for the COM ports.
None
Stop Bits (bits)
Sets the Stop Bits for the COM ports.
1
Flow Control
Sets the Flow Control for the COM ports.
None
Serial Ending Chars
The tM-752N can determine the end of the data
immediately after the ending-chars pattern is identified
from the incoming serial data.
There are some different modes can be used:
Mode 0
0x0D
(CR)
Mode 1
0x0D
+
0x0A
(CR+LF)
Mode 2
0x0A+0x0D
(LF+CR)
Mode 3
0x0A
(LF)
Mode 4
None
(Disabled)
Mode 5
User-Defined
(Note: Mode 5 can only set in web configuration)
The number of User-defined ending-char can be 1~2 chars.
For example:
1 char:
1,0x0D
;
2 chars:
2,0x0D,0x0A
4
Delimiter
This is a special symbol, placed in the front of
command/response message, can be used to identify the
legality of message.
:
Port ID
The Port ID (port address) can be used to identify each RS-
232 port; the value is the increasing value of System
address.
0
Response Timeout
For Port 1 (RS-485) in end character mode is “4” (it means
that No end character), wait for this timeout to elapse
without receiving any further data in order to determine the
end of the command.
1000
For Port 2 and 3 (RS-232), wait for this timeout to elapse
without receiving any data.
Continue Response
Timeout
Timeout value between chars of response data.
Only used for Port 2 and 3 (RS-232) in end character mode is
“4” (it means that No end character),
If the time between receiving a new character and last one
is smaller this timeout, this character can be seem as part of
a response.
0