tGW-735 tiny Modbus Gateway - QuickStart (Feb/2017)
ICP DAS USA, Inc.
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
7
8
Successful Testing
Refer to “
Protocol Description
” section and type the command in the
“Command”
field then click the
“Send command”
button. If the response data is correct, it means the test is success.
e.g., If
M-7000 Modbus device ID = 1
, you send
“1 2 0 0 0 6 1 2 0 0 4”
for reading D/I value,
you receive response
“1 2 0 0 0 4 1 2 1 0”
as shown below.
Related Information
tGW-700 product page:
http://www.icpdas-usa.com/tgw_735.html