background image

 

SMS-531 Quick Start v1.0 2013/01 

5/8

 

include   “New”, ”Open”, ”Save”, ”Save as…”, and ...etc. 

(2)

 

Language

 

The GT-531 Series Utility only support English interface now.  

(3)

 

Exit

 

Exit the GT-531 Series Utility 

(4)

 

COM Port

 

The COM number of the host PC connecting to the SMS-531  

(5)

 

Connect

 

Connecting to the SMS-531  

(6)

 

Download

 

Downloading the setting to the SMS-531 

(7)

 

Upload

 

Uploading the parameters from the SMS-531 to GT-531 Series Utility 

(8)

 

Learn

 

Providing the simple way for users to learn the Modbus RTU commands to operate SMS-531 

(9)

 

System

 

Providing some system operations include ”Signal Quality”, ”Reboot SMS-531”, ”Recover 
Default Settings”, ”Firmware Version”, ”Input PIN/PUK” and ”Voice File Management” 

2.

 

Parameter Groups

 

There  are  four  parameter  groups  in  the  GT-531  Series  Utility  including  “System”,  ”COM 
Port”, ”Phone Book” and ”Alarm Message”. 

3.

 

Parameters

 

Showing or setting the parameters  

4.

 

Status Bar 

Showing the operation procedure of the GT-531 Series Utility 
From left to right, they are: 

(1)

 

The used com port number 

(2)

 

Communication configuration of the COM Port 

(3)

 

The current status of the COM port  

(4)

 

The Modbus address of the SMS-531 

(5)

 

The result for operating the functions  

 

 

SMS-531 Modbus address Table

 

The Modbus function codes supported in the SMS-531 are 1, 2, 3, 4, 5, 6 and 16. The Modbus 

address distribution is as the following table.

 

Coil Status (Function Code:1, 5) 

Address 

Data 

Address 

Description 

Attribute 

00001 ~ 

00128 

0x0 ~ 

0x7F 

Transmitting the alarm SMS and voice according 0~127 alarm 

R/W 

00129 

0x80 

Transmitting the SMS dynamically 

R/W 

00200

 

0xC7

 

=1, clearing the received SMS buffer

 

R/W 

00201

 

0xC8

 

=1, clearing the transmitting SMS buffer

 

R/W 

00210 

0xD1 

=1, saving the data of the holding Registers (40001~40256) to 

Flash 

R/W 

Summary of Contents for SMS-531

Page 1: ...any of these items are missed or damaged contact the local distributors for more information Save the shipping materials and cartons in case you want to ship in the future Appearance and pin assignmen...

Page 2: ...oice alarm the 3G LED is continuous on Installation If users want to start SMS 531 normally it needs to follow these steps to install the SMS 531 below 1 Install the antenna 2 Plug in the normal SIM c...

Page 3: ...tart v1 0 2013 01 3 8 GT 531 Series Utility It needs the runtime environment with NET Framework 2 0 or above to execute the GT 531 Series Utility in the PC Install NET Compact Framework Install GT 531...

Page 4: ...The users need to set PIN PUK code in the GT 531 Series Utility 2 Confirm the RS232 connection between SMS 531 and PC is correct Users can refer to the following figure 3 During the setting procedure...

Page 5: ...ility including System COM Port Phone Book and Alarm Message 3 Parameters Showing or setting the parameters 4 Status Bar Showing the operation procedure of the GT 531 Series Utility From left to right...

Page 6: ...0018 0x11 The status of transmitting dynamic SMS 1 High Byte Status 0 Idle 1 System busy or waiting for transmitting 2 Transmitting 3 Transmitting OK 4 Transmitting fault 2 Low Byte Error code R 30019...

Page 7: ...0x09 0x0A Baud 38400 57600 115200 2 Low Byte Bit 2 0 Data Bit 011 8 Data Bits Bite 4 3 stop bit 00 1 stop bit 01 2 stop bit Bite 6 5 parity 00 no parity 01 odd parity 10 even parity R W 40202 0xC9 COM...

Page 8: ...r is in the groups 5 The defined phone received an abnormal SMS The SMS 531 support only Unicode SMS Confirm the defined SMS content is Unicode 6 The SMS 531 is not replied by Modbus command 1 Confirm...

Reviews: