background image

Ver1.33

2016/05/26

,~

1

 

 

SG-3013 User’s Manual   

Isolated RTD Input Module 

Introduction

 

The SG-3013 is a RTD input signal conditioning module to transform RTD input to voltage 
or current output. SG-3013 uses a microprocessor-based transducer, which integrating two 
high resolution ADCs and an MCU, to acquire the RTD signal. The supported RTD types 
are Pt100 , Pt1000 , Ni 120 , Cu100 ,and Cu1000. 
 
The SG-3013 supports 1000 V

DC

 isolation. The power supply that drives the module`s input 

and output circuitry is internally isolated. 
 
It’s easy to mount the SG-3013 on a standard DIN rail and can operate in environment with 
wide temperature range. 

 

Specifications 
Signal Input:

 

 

Input Type: 

Pt100 

α

=0.00385 / Pt100 

α

=0.003916 / Ni 120 / Pt1000 

α

=0.00385 

 

Input Connections

:2 / 3 / 4 wires 

 

RTD Type and Temperature Ranges:

 

 

 

 

 

 

 

Voltage output:

 

 

Unipolar: 0~5 V

DC

, 0~10 V

DC

 

 

Output impedance: < 50 

 

 
Current output: 

 

Current: 0~20 mA, 4~20 mA 

 

Current load resistor:0~500 

 (Source) 

 

General 

 

Three-way isolation: 1000 V

DC

 

 

Accuracy: ±0.1 % of full range 

 

Operation temperature range:-25 °C

75 °C 

 

Storage temperature range:-30 °C

85 °C 

 

Weight: 94 gram 

 

Supply Voltage   

 

Input Range: 10~30 V

DC

 

 

Consumption: < 1.2 W   

RTD Type 

α

 

Temperature range(

Pt100 0.00385 

-200~600 

Pt100 0.003916 

-200~600 

Pt1000 0.00385 

-200~600 

Ni 120 

 

-80~300 

Cu 100 at 0 °C 

α

= 0.00421 

-20~150 

Cu 100 at 25 °C 

α

= 0.00427 

0~200 

Cu 1000 at 0 °C 

α

= 0.00421 

-20~150 

Reviews: