RU-87P1/2/4/8 User Manual, Version: 1.2
59
Table 2 : The Error Code in Auto Config. Disable mode
Error
Code
Slot LED
(Red)
Status
Description
Solution
80H Dark (ok) Initialize ok
setup success
None
81H
Bright
(Error)
Internal INIT*
pin failed
The INIT Pin is failed to connect with the
GND and module failed to initialize.
If it still fails after restart the 87Pn many times,
please send the 87K I/O module back to factory
to check.
82H
Bright
(Error
)
Module
address over
255 (FFh)
The module address is over 255 (FFh).
The maximum address of
87P1 is 254 (FEh)
87P2 is 253 (FDh)
87P4 is 251 (FBh)
87P8 is 247 (F7h)
You can see the LED signals on 87Pn CPU module to know whether the 87Pn is operating properly. Please refer to appendix.
Auto Config. LED
(Green)
S.RDY LED
(Green)
Slot Status LED (Red)
Auto Config.
Enable
No Error
Always ON
Always OFF
Warning Always
ON
Flash
Failed
Always ON
Flash Always
ON
Auto Config.
Disable
No Error
Always ON
Always OFF
Failed
Always OFF
Flash Always
ON
Summary of Contents for RU-87P1
Page 33: ...3 Fig 32 Write the settings to RU 87Pn RU 87P1 2 4 8 User Manual Version 1 2 33...
Page 37: ...VB Step 3 VB Step 1 VB Step 2 Step 6 Run the project RU 87P1 2 4 8 User Manual Version 1 2 37...
Page 51: ...Appendix A Dimension A 1 RU 87P1 RU 87P1 2 4 8 User Manual Version 1 2 51...
Page 52: ...A 2 RU 87P2 RU 87P1 2 4 8 User Manual Version 1 2 52...
Page 53: ...A 3 RU 87P4 RU 87P1 2 4 8 User Manual Version 1 2 53...
Page 54: ...A 4 RU 87P8 RU 87P1 2 4 8 User Manual Version 1 2 54...