Products come with external split type clip-on CT’s. Disconnect the CT’s or use
other CT’s is highly prohibited.
Please read this operation manual carefully before using.
Please re-confirm the measure position.
Meter auxiliary power is +85 ~ +264 VAC (277 VAC available).
Wire Disconnection:
1. Open the CT clip to detach the CT, do not remove the CT terminal lines if
possible
Note: if you need to remove the terminal lines, always detach the CT before
removing the CT terminal lines.
Otherwise the CT may develop open-circuit
secondary voltages which may be hazardous to personnel or damaging to the
CT or equipment connected in the secondary circuit.
2. Disconnect the voltage input wires from terminals and wrap the wire tips with
plastic tape.
3. Disconnect the communication wires from terminal.
4. Disconnect the auxiliary power from terminal and wrap the wire tip with plastic
tape.