ICP DAS, MDC-211-ZT user manual , v1.0 Page 28
Copyright © 2018 by ICP DAS. All rights are reserved.
ZigBee Communication Settings
The first part is for ZigBee settings. ZigBee parameter descriptions may refer to "4.1.1 ZigBee
Communication Interface", the label name and setting descriptions see Table 3.1 below.
# ZigBee
# PanID
NodeID RFCH Power AES128 FrameType
*
0
0
9
8
0
0
#
Table 3.1 ZigBee settings and descriptions
Item
Label Name
Valid Code & Range
Pan ID
PanID
0000 ~ 3FFF
Node ID
NodeID
Coordinator: 0000
Router: 0001 ~ FFF7
RF Channel
RFCH
0 (2405 MHz) ~ F (2480 MHz)
RF Power
Power
0 (min.) ~ F (max.); default 8 (compatible with the
CE/FCC specification limitation)
Encryption
AES128
0 (Disable)/1 (Enable)
Frame Type
FrameType
0 (Broadcast)/1 (Unicast)
Ethernet Communication Settings
The second part is for Ethernet settings. Ethernet label name and setting descriptions please
see table 3.2 below.
#
Ethernet
#
DHCP
IP
Mask
Gateway
*
0 192.168.255.1 255.255.0.0 192.168.0.1
#
Table 3.2 Ethernet settings and descriptions
Item
Label Name
Valid Code & Range
DHCP
DHCP
0 (Disable) / 1 (Enable)
NOTE
– The IP, Mask and Gateway should be set up according to the local network.