M-7002 - 4-ch AI, 5-ch DI and 4-ch Relay Output DAQ Module - QuickStart (Jun/2018)  

ICP DAS USA, Inc.

 | 

www.icpdas-usa.com

 | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717

 

 

M-7002  

4-channel AI, 5-channel DI and 4-channels 

Relay OutputData Acquisition Module 

Quick Start Guide 

Product Website:  

https://www.icpdas-usa.com/m_7002.html

 

http://www.icpdas-usa.com/dcon_utility_pro.html

  

1. Introduction 

 

The M-7002 is a 16-bit, 4-channel differential analog inputs 5-channel digital inputs and 
4-channels for relay output. All of its channels are Form A type relay module that 
provides programmable input range on all analog channels (+/-150 mV, +/-500 mV, +/-1 
V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA and 4 ~ 20 mA) and digital output can be set 
alarm output with shortcircuit protection and overload protection. Each analog channel 
is allowed to configure an individual range and has 240 Vrms high overvoltage 
protection. Jumper selectable for voltage or current input. The sampling rate of M-7002 
is changeable; there are fast mode and normal mode for your consideration. M-7002 
also has qualification for 4 kV ESD protection as well as 2500 VDC intra-module 
isolation. 

 

2. Terminal Assignment 

 

 

 

Summary of Contents for M-7002

Page 1: ...ts and 4 channels for relay output All of its channels are Form A type relay module that provides programmable input range on all analog channels 150 mV 500 mV 1 V 5 V 10 V 20 mA 0 20 mA and 4 20 mA a...

Page 2: ...9 Narbonne Ave Suite 200 Lomita CA 90717 2 3 Block Wiring Diagram 4 Default Settings Default settings for the M 7005 modules are as follows Protocol Modbus RTU Module Address 01 Thermistor Type Type 6...

Page 3: ...l the module follow the steps below 1 Connect the thermistor analog input 2 Connect the module to the RS 485 network using the DATA and DATA terminals If the host is only equipped with an RS 232 inter...

Page 4: ...310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 4 4 Open DCON utility pro click on COM port first icon It can select multi options such as Baud Rate Protocol Checksum and Format to search mo...

Page 5: ...pdas usa com 1 310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 5 5 DCON utility pro will search for the selected COM port according the setting previously set DCON Utility Pro supports DCON...

Page 6: ...st also be sent See user manual Section 2 12 for details For M 7000 modules using the Modbus RTU protocol configure the module using the following functions Sub function 04h of Function 46h see user m...

Page 7: ...un 2018 ICP DAS USA Inc www icpdas usa com 1 310 517 9888 24309 Narbonne Ave Suite 200 Lomita CA 90717 7 8 If user doesn t know command user can select Address and ID it will show some refer commands...