LC-305 User Manual      Version 1.0.0 Jan. 2018

 

  - 

8  - 

 

 

3. Modbus Address Mapping 

Address 

Description 

Attribute 

30001 ~ 30005 

40001 ~ 40005 

Current input value of channel 0 to 4 in mA 

40481   

Firmware version (low word) 

40482 

Firmware version (high word) 

40483 

Module name (low word) 

40484 

Module name (high word) 

40485 

RS-485 module address, 1 to 247 

R/W 

40486 

RS-485 baud rate and parity settings 

Bits 5:0 

Baud rate, valid range: 3 ~ 10 

Bits 7:6 

        00: no parity, 1 stop bit 

        01: no parity, 2 stop bit 

        10: even parity, 1 stop bit 

        11: odd parity , 1 stop bit 

R/W 

40488 

RS-485 response delay time in ms, valid range, 0 

~ 30 

R/W 

00257 

Protocol, 0: DCON, 1: Modbus RTU 

R/W 

00273 

Reset status, 1: first read after powered on, 0: not 

the first read after powered on 

 
Ordering Information 

LC-305 CR 

5-channel AC Load Current Measurement Module (RoHS) 

LC-305/DIN CR 

5-channel AC Load Current Measurement Module (DIN Rail 

mount) (RoHS) 

 
Revision History 

Revision  Date 

Description 

1.0.0 

2018/Jan.  First released 

 

Summary of Contents for LC-305

Page 1: ...LC 305 User Manual Version 1 0 0 Jan 2018 LC 305 LC 305 DIN 5 channel AC Load Current Measurement Module User Manual Version 1 0 0 Date Jan 2018...

Page 2: ...of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is a...

Page 3: ...ser Manual Version 1 0 0 Jan 2018 Table of Contents 1 Introduction 1 2 Hardware 2 2 1 IO Specifications 2 2 2 System Specifications 3 2 3 Dimensions unit mm 4 2 5 Wire Connections 6 3 Modbus Address M...

Page 4: ...ided When required communication with the LC 305 is programmable based on the Modbus RTU protocol and an added benefit is that different addresses can be set via hardware configuration The module can...

Page 5: ...l Watchdog Support DCON and Modbus RTU Protocol Wide Operating Temperature Range 25 to 75 C Tiny Form Factor with Easy Screw Mounting 2 Hardware 2 1 IO Specifications Current Input Channels 5 Wiring S...

Page 6: ...indicator EMS Protection ESD IEC 61000 4 2 4 kV contact for each terminal EFT IEC 61000 4 4 4 kV for power and communication 4 kV Air for Random Point Power Reverse Polarity Protection Yes Input Volt...

Page 7: ...LC 305 User Manual Version 1 0 0 Jan 2018 4 2 3 Dimensions unit mm...

Page 8: ...LC 305 User Manual Version 1 0 0 Jan 2018 5 2 4 Pin Assignments...

Page 9: ...LC 305 User Manual Version 1 0 0 Jan 2018 6 2 5 Wire Connections DIP Switch and Jumper Settings...

Page 10: ...LC 305 User Manual Version 1 0 0 Jan 2018 7 Address Settings via Hardware Configuration 0 F for Addresses 96 111 Low Node Address 0 F for Addresses 112 127 High Node Address...

Page 11: ...tings Bits 5 0 Baud rate valid range 3 10 Bits 7 6 00 no parity 1 stop bit 01 no parity 2 stop bit 10 even parity 1 stop bit 11 odd parity 1 stop bit R W 40488 RS 485 response delay time in ms valid r...

Reviews: