background image

 

P2 

Modbus Address Mapping Table 

iWSN sensor Node ID 

The range of address 

mapping 

(Hexadecimal) 

The range of address 

mapping   

(Decimal

Base 0) 

The range of address 

mapping   

(Decimal

Base 1) 

0x

01

41~0x

01

6C 

321~364 

40322~40365 
30322~30365 

0x

02

41~0x

02

6C 

577~620 

40578~40621 
30578~30621 

 

 

 

 

30 

0x

1E

41~0x

1E

6C 

7745~7788 

47746~47789 
37746~37789 

31 

0x

1F

41~0x

1F

6C 

8001~8044 

48002~48045 
38002~38045 

For example, iWSN-100X-CLE /

 

iWSN-101X-CLE Node ID 1: 

PLC 

address 

(Base1) 

Protocol 

address 

(Base0) 

Function 

code 

Property 

Data 

type 

Description 

Remarks 

40347 
30347 

346 

(0x

01

5A) 

03, 04 

Uint16 

Mean value: X 

Measurement 

range is

0 to 8 g 

(Divide the value 
by 100) 

40348 
30348 

347 

(0x

01

5B) 

03, 04 

Uint16 

Mean value: Y 

40349 
30349 

348 

(0x

01

5C) 

03, 04 

Uint16 

Mean value: Z 

40350 
30350 

349 

(0x

01

5D) 

03, 04 

Uint16 

RMS value: X 

40351 
30351 

350 

(0x

01

5E) 

03, 04 

Uint16 

RMS value: Y 

40352 
30352 

351 

(0x

01

5F) 

03, 04 

Uint16 

RMS value: Z 

40353 
30353 

352 

(0x

01

60) 

03, 04 

Uint16 

MAX value: X 

40354 
30354 

353 

(0x

01

61) 

03, 04 

Uint16 

MAX value: Y 

40355 
30355 

354 

(0x

01

62) 

03, 04 

Uint16 

MAX value: Z 

40366 
30366 

355 

(0x

01

63) 

03, 04 

Uint16 

Composite 

vector value 

(Three-axis) 

 