background image

 

 

iSN-101 / iSN-104 

Liquid Leak Detection Module 

User Manual 

iSN-101         

 

 

        iSN-101/DIN                                  iSN-104

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

                               

 

 

 

 

   

Version: 2.3.0 

                                     

 

 

 

 

 

 

 

 

   

Date: Dec. 2022 

   
                                                                                            Edited by Jerry Tseng 

 
 
 
 
 
 

Summary of Contents for ISN-101

Page 1: ...iSN 101 iSN 104 Liquid Leak Detection Module User Manual iSN 101 iSN 101 DIN iSN 104 Version 2 3 0 Date Dec 2022 Edited by Jerry Tseng...

Page 2: ...reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is assumed by ICP DAS for it...

Page 3: ...Leak Detection Cable Relay Output 11 2 4 Pin Assignments 14 2 5 Wire Connections 15 2 6 Application 16 2 7 Dimensions unit mm 18 3 Configuration via RS 485 19 Appendix A DCON Command Sets 26 A 1 iSN...

Page 4: ...eakage Probe If liquid is detected the controller immediately activates the output relay the normally open normally closed passive output signal The module can be easily integrated with other collecti...

Page 5: ...iSN 101 104 User Manual 5...

Page 6: ...re detection A mute button to silence the alarm Two LED indicators to display the status of the power and the alarm iSN 104 have Five LED A configurable Output Relay only iSN 101 Leader cables and Liq...

Page 7: ...guration 0 255 for software configuration LED Indicators Power 1 as Power Indicator Green LED 1 as Power Indicator Red LED Alarm 1 as Alarm Indicator Red LED 4 as Alarm Indicator Red LED Audible alarm...

Page 8: ...n are Alarm red for leak alarm condition blinking red for open wire alarm condition iSN 101 Only for after 2021 Q1 FW A1 3 or later and used with CA LLD DC100X Lxxx CA LLD DC100X TR to have Open wire...

Page 9: ...stment Sensitivity Adjustment Range 26K 580K 1 ch Input Insert Leader Cable As cable termination is not polarity conscious DIP Switch Address Relay Output Wire Connection Output Type ON State Readback...

Page 10: ...LED blinking for open wire alarm condition PWR Power LED Audible alarm 70 dB Audible alarm with silence button Sensitivity Adjustment Sensitivity Adjustment Range 26K 580K 4 ch Input Insert Leader Ca...

Page 11: ...iSN 101 104 User Manual 11 DIP Switch Address 2 3 Connector for Power RS 485 Liquid Leak Detection Cable Relay Output...

Page 12: ...can be extended with a shielded twiced pair cable AWG 18 14 The total cable length that includes leader cable and Liquid Leak Detection Cables is 500 m max CA LLD DC100X TR Terminal Resistor for CA L...

Page 13: ...iSN 101 104 User Manual 13 Connect the Leakage Probe with Wires Take off cover Put wire and tighten the screw down...

Page 14: ...iSN 101 104 User Manual 14 Put cover back Install the two mounting screws into the 2 keyhole mounting holes 2 4 Pin Assignments iSN 101 iSN 104...

Page 15: ...iSN 101 104 User Manual 15 2 5 Wire Connections...

Page 16: ...tion Cable Liquid Leak Detection Cable is designed to detect leaks over a wider area and the path of the leak is not easily predetermined The Liquid Leak Detection Cable is ideal for open areas The Li...

Page 17: ...g a circuit and triggering an alarm Leakage Probe are ideal for drains Water storage tank containers and other restricted areas Stainless steel probes Water supply Liquid forming current loop trigger...

Page 18: ...iSN 101 104 User Manual 18 iSN 101 104 senses various water levels through the Leakage Probe 2 7 Dimensions unit mm iSN 101...

Page 19: ...esponse Delay ms 0 Note If there are multiple iSN 101 104 connected to the same RS 485 network each module needs be set with a unique RS 485 address More than one module having the same address will c...

Page 20: ...User Manual 20 2 Launch the DCON_Utility_Pro exe 3 Click the icon to configure the COM port 4 Select the COM Port number used to connect the iSN 101 104 logger Set COM port Configuration Start Search...

Page 21: ...iSN 101 104 User Manual 21 5 The Baud Rate is factory default to 9600 bps 6 Select the Protocol tab 7 Select the Format tab and check the parity that set in the logger...

Page 22: ...the logger Note The Protocol Baud Rate Parity Checksum items marked with INIT means that when any of those items needs be modified the pin 4 INIT needs to be set in ON position and power cycle the log...

Page 23: ...on Leakage Detect Resistance Adjust the Wire Alarm Mode Leakage Detect Resistance Adjust the Beeper On Alarm Time Threshold Index Sensitivity Leak Alarm Mode Adjust the Leak Alarm Mode Adjust the Beep...

Page 24: ...the Set WDT button to enable the Host watchdog 2 Check the checkbox next to Send Host OK to send the command 3 Uncheck the checkbox next to Send Host OK to stop sending command the Host watchdog timeo...

Page 25: ...on with the pin 4 INIT in ON position the protocol is DCON address is 0 Baud Rate is 9600 bps Parity is set to N 8 1 and Checksum is disabled After configuring the communication parameters click the S...

Page 26: ...resistance in k ohm 1 for threshold index by VR iSN 104 i 0 to 3 for channel resistance in k ohm 4 for threshold index by VR AABA Read beep on alarm time response aahh hh in hex 0 disabled 1 250 beep...

Page 27: ...0OOII AADOhh Set DO For iSN 101 Only AAEATCi Enable AI alarm of channel i T M momentary alarm L latched alarm iSN 101 i 0 for leak alarm i 1 for open wire alarm iSN 104 i 0 to 3 for leak alarm 4 to 7...

Page 28: ...configuration FF bit 6 1 checksum enabled AAB Read open wire status response iSN 101 AAHH bit 0 of HH open wire status 1 for open wire iSN 104 AAHH bit 0 to 3 of HH open wire status 1 for open wire aa...

Page 29: ...ary DIP switch aaSR Software reset aaTxx Set soft INIT timeout in s xx in hex aa0 Read host watchdog status aa1 Clear host watchdog timeout status aa2 Read host watchdog setting aa3ett Set host watchd...

Page 30: ...de 0x03 0x04 0x05 0x06 Baud 1200 2400 4800 9600 Code 0x07 0x08 0x09 0x0A Baud 19200 38400 57600 115200 Bits 7 6 00 no parity 1 stop bit 01 no parity 2 stop bits 10 even parity 1 stop bit 11 odd parity...

Page 31: ...nd diagnosing the wiring It is located in the company CD CD Napdos iSN 101 104 utility and needless to install This section intends to guide the steps for creating the Modbus communication with iSN 10...

Page 32: ...al 32 4 Select Connect in the Connection menu 5 Select the communication interface When using RS 485 as the interface select the COM port check the RTU mode and click on the OK button 6 Select Definit...

Page 33: ...iSN 101 104 User Manual 33 7 Select the Modbus function code input the start address and length and click on the OK button 8 Read data...

Page 34: ...9 Write data to Holding Register or Coil Status 1 Highlight the Modbus address in the Holding Register or Coil Status list 2 Select Set Value in the Setup menu 3 Input the data in the Value box and c...

Page 35: ...RS 485 module address 1 to 247 R W 40486 RS 485 baud rate and parity settings Bits 5 0 Baud rate valid range 3 10 Bits 7 6 00 no parity 1 stop bit 01 no parity 2 stop bit 10 even parity 1 stop bit 11...

Page 36: ...us RTU R W 00260 Modbus RTU host watchdog mode 0 same as I 7000 1 can use AO and DO command to clear host watchdog timeout status Only for Modbus RTU protocol R W 00261 RS 485 host watchdog mode 1 ena...

Page 37: ...y R W 00337 00340 Leak alarm type momentary or latched of leak sensor 0 to 3 iSN 101 0 R W 00338 Alarm type momentary or latched of open wire for iSN 101 only R W 00341 00344 Open wire alarm type mome...

Page 38: ...sed 1 1 0 2021 11 Add open wire function iSN 101 for firmware version A103 and later only Add iSN 104 2 0 0 2022 02 Update 2 1 0 2022 08 Update Relay Output specification 2 2 0 2022 09 Update iSN 104...