Getting Started:
PAC-5007(P)/5107(P)/5207/5307 Ver. 1.0, 07/2010 ICP DAS
.
3-17
3.11 Set I-7000 and I-87K Remote I/O by DCON Utility
μPAC-5x07(P) can link up to 128 pcs ICP DAS's remote I/O modules - "I-7000" and
“I-87K” series remote I/O modules.
Pre-set :
Before linking I-7000 and I-87K modules, user must use DCON Utility to pre-set each
I-7000 and I-87K remote module to has a unique address (NET-ID) and the same Baud
rate (included the PAC) in this μPAC-5x07(P) PAC system.
The DCON Utility is a toolkit that helps user to search the I/O network, easily to
configure and test the I/O modules. For DCON Utility program and manual please reach
to
ftp://ftp.icpdas.com.tw/pub/cd/8000cd/napdos/driver/dcon_utility/
Step 1: Hardware Connection
Note:
The power supply must be DC power b10V ~ +30V.
Search and configure the modules one by one.
Wire Connection for I-7000 : (Configure one module at once)
Wire Connection for I-87K : (Configure one module at once)
Summary of Contents for I-8417
Page 46: ......