I-7530A-MR Modbus RTU to CAN Converter Quick Start User Guide (Version 1.0, May/2011)  ------ 4

 

3.   I-7530A-MR Parameter Configuration 

Before starting the I-7530A-MR converter tests, users need to 

configure the RS-232/485/422, Modbus and CAN parameters via the 
UART2CAN Utility tool. The details of this procedure are shown below. 

 

Step1: Turn off the DC power connected with these two I-7530A-MR 

modules. 

Step2: Set the Init/Normal switches on the back of the I-7530A-MR_A to 

the “Normal” position. Then, turn on the DC power. Afterwards, set 
the Init/Normal switches to the “Init” position and hold it at least 3 
seconds.  The CAN LED and UART LED of the I-7530A-MR_A will 
flash approximately once per second.  That means that the I-
7530A-MR is working in the configuration mode. 

Step3: Run the UART2CAN Utility. The “UART2CAN Utility.exe” is 

located on the fieldbus_cd\can\converter\I-7530A-MR\utility folder 
on the product CD-ROM or is downloaded from the web site:  

 

which are used to be communicated with the I-7530A-MR_A. 
When the Utility starts, the following dialog will be popped up. The 
default setting of the PC COM port field is configured at 
115200bps, 8 Data Bits, 1 Stop bit, and no parity.  

 

 

 

 
Step4: Select the proper PC COM port No., baud rate and data format, 

Summary of Contents for I-7530A-MR

Page 1: ...ction The goal of this manual is focused on helping users to quickly familiarize themselves with the I 7530A MR module and the data exchanged between RS 232 485 422 and CAN communication interfaces He...

Page 2: ...Installation Users need to make a hardware connection between the two I 7530A MR modules before the application The details of this are illustrated below Step1 Set up the 120 terminator resistor of t...

Page 3: ...connection Connect the RS 232 ports of the I 7530A MR_A and I 7530A MR_B to the RS 232 COM1 and COM2 of the PC by using the attached cable CA 0910 respectively You can use the attached cable CA 0910...

Page 4: ...set the Init Normal switches to the Init position and hold it at least 3 seconds The CAN LED and UART LED of the I 7530A MR_A will flash approximately once per second That means that the I 7530A MR i...

Page 5: ...ul the UART2CAN Utility will show the communication information of the I 7530A MR_A module as shown in the following figure Step6 Set the communication mode of the I 7530A MR_A Here use Modbus TRU mod...

Page 6: ...rter with the same configurations as the I 7530A MR_A 4 Testing the I 7530A MRs Step1 Turn off the DC power connected with these two I 7530A MR modules Step2 Set the Init Normal switches on the back o...

Page 7: ...U command and send it out through the PC RS 232 COM1 port After the I 7530A MR_A receives this command it will convert the Modbus RTU message to the CAN message and send it to the CAN network While th...

Page 8: ...I 7530A MR Modbus RTU to CAN Converter Quick Start User Guide Version 1 0 May 2011 8 Utility A 5 9 8 7 6 Utility B...

Reviews: