I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.08, 07/2019) ------------- 53
4.8
P2BBBBB[CHK]<CR>
Description:
Change the user-defined CAN baud rate configuration of I-7530A-
MR module and then reboot the I-7530A-MR module.
Syntax: P2BBBBB[CHK]<CR>
P2
Command character
BBBBB
User-defined CAN baud rate
Response:
A valid command will write the user-defined CAN baud rate
configuration into the EEPROM and then reboot the I-7530A-MR module.
Invalid command: ?<Error Code><CR>
Note:
It is necessary to enable the
“Error Response” function while using
the UART2CAN Utility in order to receive Syntax and/or communication
error information. Furthermore, the value of BBBBB is the baud rate value
multiplied 1000 and then converted into HEX format. For example, assume
that users want to set the CAN baud rate as 83.333 kbps. The value
BBBBB is the hex format of the value14585 (83.333 x 1000).
Example:
Command: P214585<CR>
Set the CAN baud rate=83.333 kbps into the I-7530A-MR module
and then reboot the I-7530A-MR module.
.