5. Firmware Update
Please follow the below steps to update the firmware of HRT-227CS.
Step 1
:
Power off the HRT-227CS.
Step 2
:
Set the value of dip switch (mode) to be 3. Then connect the COM port between
PC and the HRT-227CS together with CA-0910 cable like Figure 5-1.
(1) Connect the TXD / RXD / GND pins together between PC and HRT-227CS.
Figure 5-1 RS-232 wire connection between PC and HRT-227CS
Step 3
:
Power on the HRT-227CS. In firmware update mode, the HT_Err, HT_Tx,
HT_Rx LEDs will flash every 500ms.
Step 4
:
Execute
“FW_Update_Tool”
(Download
:
http://ftp.icpdas.com/pub/cd/fieldbus_cd/hart/converter/hrt-227CS/firmware/
and follow the below steps to complete the firmware updating process.
[1] Choose “
COM
” interface and “COM Port” number (like
:
COM1).
[2] Click “
Browser
” button to choose FW file. (like
:
HRT227CS_v1.00.fw)
[3] Click “
Firmware Update
” button to start the FW update process.
=>
The result will show in “Firmware Update” field.