GW-7552  PROFIBUS/MODBUS  GATEWAY  Quick  Start  User  Guide

 (Version 1.00)      

PAGE

PROFIBUS connection 

Here  we  recommend  users  to  use  the  standard  PROFIBUS  cable  and 
connector  (DB9  male).  It  is  only  needed  to  use  D-type  connector  via 
PROFIBUS  cable  to  connect  PROFIBUS  master  station  and  GW-7552 
module. PROFIBUS master station and GW-7552 module belong to terminal 
equipments in this example, thus we need to enable the terminator resistor in 
the D-type connector. 

 

Address setting 

The GW-7552 is a slave device of PROFIBUS DP protocol. The station address 
of GW-7552 can be set by dip switch. The dip switch can be seen by open the 
cover,  as  shown  in  the  below.  The  range  of  dip  switch  is  0~126,  here  we  set 
GW-7552 module’s dip switch to 1. 

 

 

  

 

LED status indicator 

LED   

Status 

Description 

flash 

When  the  GW-7552  is  as  a  Modbus  slave  device  and  receiving 
query message form Modbus master device, PWR led will flash. 

on 

Power supply is ok. 
The firmware has loaded. 

PWR 

off 

Power supply has failed. 

flash 

When  the  GW-7552  connects  with  the  utility  tool,  it  will  flash 
fast (flash once about 55ms). 
When the GW-7552 has diagnostic message, it will flash slowly 
(flash once about 220ms). 

ERR 

on 

The  connection  is  error  with  PROFIBUS  master  device  or 
PROFIBUS system configuration is not correct. 

DIP SWITCH(SW1) 

Station 

address

 

  

 

10 

31 

 

Summary of Contents for GW-7552

Page 1: ...cher is used The configuration and communication is done by the program SyCon provided by Hilscher Application example of PROFIBUS to Modbus In this example the GW 7552 acts as a Modbus slave device W...

Page 2: ...he dip switch can be seen by open the cover as shown in the below The range of dip switch is 0 126 here we set GW 7552 module s dip switch to 1 LED status indicator LED Status Description flash When t...

Page 3: ...rom the CD of the GW 7552 module into the Profibus configuration tool File CopyGSD Directory CD PROFIBUS GATEWAY GW 7552 GSD the example of how to load GSD file Here we use the hilscher CIF50 PB PROFI...

Page 4: ...er to user manual section 4 3 The Configuration of the common parameters Click Parameter Data button to enter the Parameter Data dialog Double click the GW 7552 s icon to enter the Slave configuration...

Page 5: ...ut Relay Coil 1 32 Bytes Output Register 1 64 Words Input module Input Relay Coil 1 32 Bytes Input Register 1 64 Words In this example we configure a system setting module an Output Relay Coil 2 Byte...

Page 6: ...rned on That shows the GW 7552 working in the data exchange mode Click Online Download to download the setting into PROFIBUS master station 5 GW 7552 module communication test This demo uses utility M...

Page 7: ...low Send modbus command output data FF FF Receive 0xFF in input data area of Profibus master station Module Byte Data type Representation Value Input 0 Byte Hex 0xFF Input module Input 1 Byte Hex 0xFF...

Page 8: ...d button to send Modbus command again Then MBRTU can receive response message 01 02 02 FE DC F8 41 In this message the user can know the value of DI0 DI1 have changed into 0xFE 0xDC in the GW 7552 as...

Reviews: