Understanding the Hardware Specifications
Before installing the hardware, you should have a basic understanding of hardware
specification and the wiring diagrams.
Specifications
:
:
:
:
Interface
Connector
2-pin Terminal Block
Baud Rate (bps)
1200
Isolation
1500
V
DC
DALI
Build-in DALI power
DC 16
V
DC
± 5%, max. current 250 mA
(Enabled/Disabled via a switch)
COM Port
RS-485/RS-232
Connector
3-pin Terminal Block (D+, D-, GND/TxD, RxD, GND),
Jumper Selectable
Transmission Distance (m) Depends on Baud Rate
Baud Rate (bps)
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
UART
Protocol
DCON, Modbus RTU
Connector
USB Type B
Transmission Speed
12M bps
Specification
USB 1.1 and USB 2.0 standard compatible
OS Support
Windows XP (32/64 bit), Windows 7 (32/64 bit)
USB
Protocol
DCON and Modbus RTU via Virtual COM port
LED Indicators
System LED Indicators
PWR/RUN/ERR LED
EMS Protection
ESD (IEC 61000-4-2)
±4 kV contact for Each Terminal, ±8 kV Air for Random
Point
EFT (IEC 61000-4-4)
±4 kV for Power Line
Surge (IEC 61000-4-5)
±2 kV for Power Line
Power
Power Supply
Unreg10 V
DC
~ +30 V
DC
Connector
3-pin Terminal Block
Protection
Power Reverse polarity protection, Overvoltage