background image

Symptom

Remedy

No display

Check for 24 VAC at thermostat; display is blank when 24 VAC is not 
present

System fan does not come on 
properly

Verify wiring is correct, check Gas/Electric Configuration  
(see Setting 7)

All thermostat buttons are inoperative

Verify 24 VAC is present; unit locks out when 24 VAC is not present

No response with first button press

First button press activates backlight only

Thermostat turns on and off too 
frequently

Adjust temperature differential (see Configuration Mode Setting 2)

Fan runs continuously

Press FAN (right) button to turn fan off

Status indicator light not on during call Turn status indicator function on (see Configuration Mode Setting 19)

Room temperature is not correct

Calibrate thermostat (see Configuration Mode Setting 15) 
If remote sensor is used, check S1 and S2 terminal connections

displays when any button is 
pressed

Thermostat has the button lockout function activated (see Lockout 
Feature and Configuration Mode Setting 12)

on display instead of room 
temperature

Check for a bad connection at S1 and S2 terminals, if used (see 
Configuration Mode Setting 17)

Heat or Cool not coming on

Verify wiring is correct, gently pull on each wire to verify there is a good 
connection at terminal block

Problem not listed above

Press Reset button once*

* Reset Button Function

Time and day are reset, configuration settings are unchanged.

Troubleshooting

19. 

Status Indicator Light

 (Led 0, 1, 2, 3) 

 

0 = Status indicator never on

 

1 = Status indicator on with first stage

 

2 = Status indicator on with second stage

 

3 = Status indicator on with third stage

 

Press the 

up

 or 

down

 button to select.

 

Press the 

CONFIG

 button for 2 seconds to exit configuration.

OFF

18. 

Cooling Fan Delay Off Time

 (0, 30, 60, 90 seconds) 

 

Select the fan purge time for cooling.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

LIAF059

SimpleSet

TM

 Field Programming

This feature is used for transferring configuration and program schedule from the master to the target thermostat. 
All thermostats for a job can be mounted and powered up. Configure and program one thermostat. This will be the 
master. The master will be used to copy the program to the rest of the thermostats.

Preparing the master to Send:

1.  The master must be powered with 24 VAC.
2.  Verify the master thermostat is in 

OFF

 mode.

3.  Press 

SYS

 (left) button until 

OFF

 mode displays.

4.  Remove cover of the master thermostat by gently pulling near one of the corners at the 

top of the thermostat.

 

 

Note:

 

Do not force open. Use a small coin or slotted screwdriver to release tabs if 
necessary.

5.  Press the 

up

 and 

down

 buttons and 

CONFIG

 switch simultaneously for 5 seconds.

6.  The 

OUT

 screen displays indicating the master thermostat is ready to 

transfer data.

 

 

Note:

 

Press the 

up

 and 

down

 buttons and 

CONFIG

 switch simultaneously for 5 

seconds to exit from data transfer mode and to return the master to the 

OFF

 

mode.

7.  Turn off power to the master and remove it from the wall.
8.  Connect the master to the target using the 3 wire connector. Attach one end to the 

Master’s FP pins and the other end to the Target’s FP pins.

 

 

Note:

 

Target thermostat must be powered with 24 VAC for field programming to occur

When the connection has been made correctly, the master thermostat will power  
up and the target will count from 5 down to 1. It will then display the 

LOCK

 confirming the data 

has been saved in memory.
When all target thermostats have been completed, reinstall the master thermostat.
Press the 

up

 and 

down

 buttons and the 

CONFIG

 switch simultaneously for 5 seconds to exit from the data transfer 

mode and to return the master thermostat to the 

OFF

 mode.

Requires SimpleSet

TM

 Transfer Cable (ACC-WIH21)

OFF

FP pins

8. 

Dual Fuel System –

 Appears only if heat pump is selected. 

 

1 = Heat pump with gas/oil furnace backup

 

0 = Heat pump with electric backup

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

9. 

Outdoor Upper Setpoint 

(50°F to 25°F, – –) (10°C to -4.0°C, – –) 

 

Appears only if heat pump is selected.

 

 

Note:

 

See chart on below for more information 

 

For Heat Pumps With Gas/Oil Backup

 

When the ambient temperature is below the selected temperature, the heat pump will 
be locked out and only the furnace will operate. 

 

For Heat Pumps With Electric Backup

 

When the ambient temperature is above the selected temperature, the heat pump will 
operate and electric backup will be locked out. 

 

Press the 

up

 or 

down

 button to select temperature.

 

Press the 

right

 button to advance to the next screen.

10. 

Outdoor Lower Setpoint

 (select – – to disable)

 

Appears only for heat pump with electric backup with outdoor upper setpoint enabled.

 

 

Note:

 

See chart below for more information

 

When the ambient temperature is below the selected temperature, heat pump is 
locked out and only electric heat will operate 

 

Press the 

up

 or 

down

 button to select temperature.

 

Press the 

right

 button to advance to the next screen.

 

See “Remote Sensor When Used as Outdoor Sensor” diagram below.

17. 

Temperature Sensor

 (1-3) 

 

Appears for non-heat pump systems and heat pumps without an  
outdoor sensor. 

 

1. Only on-board sensor determines room temperature.

 

2. Only remote sensor determines room temperature.

 

3. Average temperature of on-board and remote sensor.

 

 

Note:

 

If there is no remote sensor, option 1 must be selected.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

16. 

Maximum Cycles Allowed Per Hour

 (- -, 2-6) 

 

  - - = as many as needed, 2-6 = maximum cycles/hour

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

15. 

Room Temperature Offset

 (+9°F to -9°F) (+4.5°C to -4.5°C) 

 

Adjust to calibrate displayed room temperature to match actual room temperature. 

 

 

Note:

 

When not set to 0, 

 

will display

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

12. 

Lockout

 (0-8°, COOL-HEAT)

 

Select the number of degrees set temperature can be changed during keypad lockout. 

COOL-HEAT

 lockout allows adjustment of the set temperatures to the maximum heat 

set temperature selected in Step 13 and minimum cool set temperature selected in 
Step 14.

 

 

Note:

 

The mode cannot be changed when the thermostat is locked.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

13. 

Maximum Heat Setpoint

 (45°F to 90°F) (7°C to 32°C) 

 

Adjust to control the maximum heat set temperature allowed.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

14. 

Minimum Cool Setpoint

 (45°F to 90°F) (7°C to 32°C) 

 

Adjust to control the minimum cool set temperature allowed.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

11.  Auxiliary Delay ON

 (0-30 minutes)

 

Set the delay time in minutes for auxiliary heat to be locked out after a call for second 
stage. This extra savings feature is used to temporarily lock out auxiliary heat devices, 
allowing just heat pump to try to satisfy heat call.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right 

button to advance to the next screen.

Remote Sensor When Used as Outdoor Sensor

Heat Pump with 
Electric Backup

Heat pump operation only

Both heat pump and 

electric backup

Electric backup only

Upper setpoint

Lower setpoint

°F/C

Outdoor 

Temperature

Outdoor 

Temperature

Upper setpoint

Heat pump operation only

Gas/oil operation only

°F/C

Heat Pump with 
Gas/Oil Backup

Mode of Operation

The 

SC4812

 is an auto changeover, 3-stage heat, 2-stage cool thermostat. It functions with air conditioning, heat 

pumps, gas, oil or electric heat systems. It is dual fuel compatible and an outdoor sensor can be used to monitor the 
crossover temperature.

The thermostat activates the heating appliance when the room temperature is below the set heat temperature 
(by the differential temperature) and the red indicator light (configurable) on the thermostat will light. The 

SC4812

 

will stop outputting and the red light will turn off when the call for heat has been satisfied. With heat pumps, the 
thermostat will not let the compressor come on for 4 minutes after it turns off. This protects your compressor.

When the room temperature is greater than the set cool temperature (by the differential temperature), the cooling 
device is activated and the green indicator light (configurable) on the thermostat will turn on. The 

SC4812

 will 

stop outputting and the green light will turn off when the call for cooling is satisfied. The thermostat will not let the 
compressor come on for 4 minutes after it turns off. This protects your compressor.

The 

SC4812

 has four possible operating modes: 

OFF

Heat

Cool

, and 

Heat & Cool

 mode. In off mode, the 

thermostat will not turn on heating or cooling devices. The manual fan can be turned on in all operating modes using 
the fan button. In heat mode, the thermostat controls the heating system. In the cool mode, the thermostat controls 
the cooling system. In heat & cool mode, the thermostat controls both the heating and cooling systems. The clock 
display alternates with the set temperature display for heat & cool mode.

The 

SC4812

 also has a button lockout feature. This enables the thermostat to be set to the proper mode and 

temperature and locked so it cannot be tampered with.

Operating Modes

There are four possible operating modes for the 

SC4812

. Off, Cool, Heat, and Cool & Heat modes are accessed by 

pressing the 

SYS

 (left) button. 

OFF Mode

•  In this mode, the thermostat will not turn on the heating or cooling devices
 

 

Note:

 

The indoor fan can be turned on manually in every operating mode by 
pressing the FAN (right) button. The word FAN shows on the display and 
the fan icon   appears when the fan operates.

OFF

Heat Mode

•  In this mode, the thermostat controls the heating system. When the heat outputs, 

the flame icon   apprears on the display.

 

 

Note:

 

For heat pumps, there is a four minute delay for your compressor to 
restart after it has turned off. To bypass the compressor time delay, go to 
OFF mode for 5 seconds.

Emergency Heat Mode (Heat pump systems only)

•  In emergency heat mode, the heat pump system will be disabled and auxiliary 

heat will become the primary source of heat.

Button Functions

UP

Used to increase the time, set temperatures and to adjust configuration settings. 

DOWN

Used to decrease the time, set temperatures and to adjust configuration settings.

SYS (left)

Used to change from OFF, HEAT, EMERGENCY HEAT, COOL and AUTO changeover modes

FAN (right)

Used to turn on and off the indoor fan.

UP, SYS and FAN

Held in simultaneously for 10 seconds to lock and unlock the thermostat.

DOWN and SYS

Pressed simultaneously to display outdoor temperature if outdoor remote sensor is connected.

SYS

tem (left)

FAN

 (right)

Down

 button

Up

 button

Cool Mode

•  In this mode, the thermostat controls the cooling system. When the cooling 

outputs, the snowflake icon   apprears on the display.

 

 

Note:

 

There is a four minute delay for your compressor to restart after it has 
turned off. To bypass the compressor time delay, go to OFF mode for 5 
seconds.

Cool and Heat Mode (Auto Changeover)

•  In this mode, the thermostat controls the cooling and heating systems, automatically 

changing over from one to the other as needed.

•  The timing display alternates with the set temperature every 10 seconds in the cool 

and heat mode.

Lockout Feature

The 

SC4812

 has a button lockout feature so the mode cannot be changed and the 

temperature adjustment is limited. Select the appropriate lockout from Configuration 
Mode Settings (Step 12) of this guide.
To activate the LOCK feature:
1.  Simultaneously press the 

SYS

FAN

 and 

UP

 buttons for 10 seconds.

2.   will display and the lockout function will be enabled.
To deactivate the LOCK feature, repeat steps 1 and 2 above.

Testing the Thermostat

Once the thermostat is configured, it should be thoroughly tested.

 

CAUTION!

Do not energize the air conditioning system when the outdoor temperature is below 50 
degrees. It can result in equipment damage or personal injury.

Heat Test

1.  Press 

SYS

 (left) button until heat mode is displayed.

2.  Adjust the set temperature so it is 5 degrees above the room temperature.
3.  Heat should come on within a few seconds. Red LED may turn on.
4.  Adjust the set temperature 2 degrees below the room temperature and the heat should  

turn off. There may be a fan delay on your system.

 

 

Note:

 

For heat pumps, there is a four-minute delay to protect your compressor after 
it turns off. To bypass the compressor time delay, go to 

OFF

 mode for 5 seconds.

Cool Test

1.  Press 

SYS

 (left) button until cool mode is displayed. 

2.  Adjust set temperature so it is 5 degrees below room temperature.
3.  A/C should come on within a few seconds. Green LED may turn ON.
4.  Adjust the set temperature 2 degrees above the room temperature and the A/C should 

turn off. There may be a fan delay on your system.

 

 

Note:

 

T

here is a four-minute time delay to protect the compressor after it turns off.

 

 

To bypass the compressor time delay, go to 

OFF

 mode for 5 seconds.

Fan Test

1.  Press 

FAN

 (right) button. Fan displays. Indoor fan turns ON.

2.  Press 

FAN

 (right) button. Indoor fan turns OFF.

Patent No. 424,953

7313 William Barry Blvd., North Syracuse,  NY  13212

(

Toll Free) 800-365-5525     (Phone) 315-233-5266     (Fax) 315-233-5276

www.icmcontrols.com

FIVE-YEAR LIMITED WARRANTY

The Seller warrants its products against defects in material or workmanship for a period of five (5) years from the 
date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for 
the purchase prices of the goods which are provided to be defective. The warranty and remedies set forth herein 
do not apply to any goods or parts thereof which have been subjected to misuse including any use or application 
in violation of the Seller’s instructions, neglect, tampering, improper storage, incorrect installation or servicing not 
performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify 
the Seller promptly of any claim, submitting date code information or any other pertinent data as requested by the 
Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective 
and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection fee. This warranty 
constitutes the Seller’s sole liability hereunder and is in lieu of any other warranty expressed, implied or statutory. 
Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or described herein are fit for 
any particular purpose.

Reviews: