ICM Controls ICM870-32A Installation, Operation & Application Manual Download Page 2

LIAF312

800.365.5525

7313 William Barry Blvd., North Syracuse, NY 13212
www.icmcontrols.com

INSTALLATION

INSTALLATION

Softstart

R S

C

OL

L2

L1

T2

Remove the Compressor 

Run Winding Wire from T2 

of the Contactor and Splice 

to the ICM870 Brown Wire

NOTE 

(Step 2A)

Compressor 

Contactor

Control 

Voltage

Line 

Voltage

Co

il

T1

Compressor

Black

Blue

Brown

Splice 

(Step 2B)

Red

Run

Cap

C

H

Legend:

S = Start

C = Common

H = Hermetic

R = Run

OL = Overload Switch

!

!

WIRING DIAGRAM (GENERAL LAYOUT)

WIRING DIAGRAM (GENERAL LAYOUT)

FOR

 RESIDENTIAL A/C

’s

FOR

 RV & MARINE A/C

’s

Softstart

R S

C

OL

L2

L1

Compressor

Black

Blue

Brown

Splice 

(Step 1B)

Red

Run

Cap

Legend:

S = Start

C = Common

H = Hermetic

R = Run

OL = Overload Switch

C

H

!

NOTE 

Remove the Compressor Run Winding Wire from 

Common (C) of the Run Capacitor and Splice to the Brown Wire of 

the ICM870 Soft Start

!

Step 1A

WHICH MODEL DO I NEED?

ICM870-9A: For AC’s with a Compressor Rated Load Amps (RLA) of up to 9A
ICM870-16A: For AC’s with a Compressor Rated Load Amps (RLA) of 9.1-16A
ICM870-32A: For AC’s with a Compressor Rated Load Amps (RLA) of 16.1-32A

This chart reflects average conversions of Single-Phase Air Conditioning and 
Heat Pump Tonnage, BTU’s, HP, and RLA. Please refer to you user manual 
or service panel to determine your actual RLA before deciding which model 
ICM870 you need.

Air Conditioning & Heat Pump Loads – Average

Size 

BTU 

RLA 

ICM870 Model

1 Ton 

12,000 

6

9A

2 Ton 

24,000 

12

16A

3 Ton 

36,000 

16

16A

4 Ton 

48,000 

22

32A

5 Ton 

60,000 

26

32A

6 Ton 

72,000 

32

32A

Step #1  Connect the (ICM870 RED WIRE) 

>

 to the run capacitor 

terminal (c/common/T2)

Step #2  a) Disconnect factory installed compressor run wire from the  

     contactor terminal (T2/L2)
b) Splice the (ICM870 BROWN WIRE

>

 to the compressor 

run wire previously disconnected in (Step 2A)

If there is a Start Capacitor and or PTCR already in place, 

additional steps will be required to disconnect.

Step #3  Connect the (ICM870 BLUE WIRE

>

 to the run capacitor 

terminal (herm/hermetic/start)

Step #4  Connect or splice the (ICM870 BLACK WIRE

>

 to the 

contactor terminal (T1)

Step #1  a) Disconnect factory installed compressor run wire from the 

common run capacitor / L2 terminal

b) Splice the ICM870 BROWN WIRE > to the factory installed 

compressor run wire previously disconnected in step #1A.

If there is a Start Capacitor and or PTCR already in place, 
additional steps will be required to disconnect them.

Step #2  ICM870 RED WIRE > to the run capacitor (c/common/L2) 

terminal

Step #3  Connect the ICM870 BLUE WIRE > to the run capacitor 

(herm/hermetic/start) terminal

Step #4  Splice the ICM870 BLACK WIRE > with the factory install 

compressor Overload Switch wire (OL/L1)

Special attention should be made with respect to the termination of the field wiring leads. When these leads are terminated at a 

terminal, they shall terminate only at a terminal suitable for minimum 90°C wire.