ICM870-32A
Soft Start
START = Green • RUN = Green • FAULT = Red (flashing)
Semi-Conductor Soft-Start Motor Controller, Form 2, Bypassed Controller
• SCCR: 5kA
• Uimp = 4kv
• Ue = 240 VAC
• Pollution degree 3
• Ui = 240 VAC
Input (L1, L2) – 100-240 VAC 50/60Hz
• Over voltage limits: 115 VAC nominal = 140 VAC,
240 VAC nominal = 264 VAC
• Under voltage limits: 115 VAC nominal = 95 VAC,
240 VAC nominal =195 VAC
Outputs: Compressor
• Solid state/relay
• Current: Max. nominal = 32A
• Over current limits: ICM870-32A = 40A
Environmental:
• Ambient temperature:
40°C @ 32 FLA, 8 hour duty
• Storage temperature: -40°F to 149°F (-40°C to 65°C)
• Humidity: 0-95% non-condensing
• Enclosure: IP65
• Dimensions: 7.94” x 4.20” x 2.10”
• Screw hole center points: 7.36” x 2.97”
HIGH VOLTAGE WARNING – Always turn off power at the main
service panel before installing.
CAUTION:
The ICM870-32A must be mounted in an area where it will
not be exposed to water or the elements. Exposure of the ICM870-
32A soft start to water can cause failure of the control and is a risk for
fire or other electrical safety hazards.
Suitable for use on a circuit capable of delivering not more than 5,000
rms symmetrical Amperes, 240 V maximum when protected by a
circuit breaker having not more than 40 A, 240 volts maximum
Installation of any ICM870-32A soft start must be done by a certified
HVAC technician or licensed electrician. All installations are to be
done in accordance with local, state, and national electrical codes.
The ICM870-32A is intended for Marine, Recreational Vehicle, HVAC
and commercial applications. The ICM870-32A integrates compressor
in-rush current over startup time, thus reducing peak current demand
on a power supply source (generator or other). The ICM870-32A
will monitor system health including voltage, current, compressor
startup and self integrity. Upon a fault condition, the ICM870-32A will
halt operation and initiate a 3 minute anti-short cycle routine while
providing diagnostic fault information by means of an LED indicator.
The ICM870-32A model crosses to the comparable amperage models
from the following manufacturer’s:
• Micro-Air (Easy Start)
• Network RV (Soft Start)
• Dometic (Smart Start)
• Hyper Engineering (Sure Start)
Starting current reduction and
self-learning algorithm
Built-in start capacitor
Over-current protection
Over/under voltage
monitoring
Diagnostic indicators
Sealed enclosure
• UL 60947-1
• UL 60947-4-2
• Altitude: 2000 m
• IP65
• CSA C22.2 NO. 60947-1
• CSA C22.2 NO. 60947-4-2
Fault Code
Fault Condition
1
High or low voltage
2
Compressor not sensed or open fuse
3
High current
4
Compressor start error
5
Invalid operating frequency
INSTALLATION, OPERATION & APPLICATION GUIDE
For more information on our complete range of American-made products – plus
wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com
IMPORTANT SAFETY INFORMATION
SPECIFICATIONS
STANDARD AND TEST RESULTS
FAULT CODES
ICM870-32A COMPARABLE AMPERAGE CROSSES
FEATURES
APPLICATION
LED INDICATORS