!!! DANGER !!!

 

Verify power is disconnected by removing a fuse or opening a circuit breaker before making 
any connections or injury or death can result.

1.  Disconnect power. 
2.  Mount 

ICM492

 securely against  the metal chaises of the system in a water proof environment.  

3.  If a contactor or a relay is used in the system (see Fig.1) to control power to the load then: 
  a.  Make L1 and L2 connections.
  b.  Cut the wire that powers the contactor/relay coil, strip and place 1/4” female spade terminals on them. 
  c.  Plug female spade terminals on COM and N.O. terminals of 

ICM492

4.  Should you choose to drive the load directly (see Fig.2) using relay contacts of 

ICM492

 then:

  a.  Make sure that load current rating does not exceed current rating of 

ICM492

 relay contacts.

  b.  Cut the line that powers the load, strip and place 1/4” female spade terminals on them.
  c.  Plug female spade terminals on COM and N.O. terminals of 

ICM492

5.  Should you choose to use a control signal at Control Voltage input terminals then:
  a.  Use two wires with 1/4”female spade terminals on them to plug on Control Voltage terminals of 

ICM492

.

  b.  Tap into control signal with the other end of the wires.
6.  Press SELECT button to enter the select menu.
a.  Use Up and Down arrows to adjust feature settings.
b.  Make sure that the Control Mode is ON if the control signal is used at Control Voltage terminals.

INSTALLATION

WIRING DIAGRAMS

Figure 1

Figure 2

Motor

* Not necessary but recommended 1 Amp fuse.

Press SELECT to enter menu setup

•  VOLTAGE SET POINT displays (95 – 280 VAC)
•  Adjust this to match the voltage of your system.
•  Use 

up

 or 

down

 button to adjust.

Press SELECT for next screen

•  TIME DELAY (Lockout) displays (1-720 seconds)
•  This is the amount of time your system will be locked 

out after a fault.

•  Use 

up

 or 

down

 button to adjust.

Press SELECT for next screen

•  OVER VOLT PERCENTAGE displays (5-25%)
•  This is the percent the actual voltage must be above 

your Set Voltage for an over fault to occur.

•  Use 

up

 or 

down

 button to adjust.

Press SELECT for next screen

•  UNDER VOLT PERCENTAGE displays (5-25%)
•  This is the percent the actual voltage must be below 

your Set Voltage for an under fault to occur.

•  Use 

up

 or 

down

 button to adjust.

SELECT MENU SETUP

Press SELECT for next screen

•  CONTROL MODE displays (OFF - ON)
•  When set to ON, the relay contacts close only when 

line voltage conditions are good and voltage is 
present at the Control Voltage terminals.

•  Use 

up

 or 

down

 button to adjust.

Press SELECT for next screen

•  RESPONSE TIME displays (.01-10 seconds)
•  This is the amount of time the fault condition must 

exist before your system is turned off.

•  Use 

up

 or 

down

 button to adjust.

Press SELECT for next screen

•  FAULT 1 - 5 displays 
•  This is the voltage of the fault that has occurred.
•   – – – Indicates no fault is in memory

NOTE:

 

Faults can be cleared by simultaneously 
pressing the UP, DOWN and SELECT buttons 
after exiting SELECT Menu Setup.

After 15 seconds of button inactivity, the control exits 

SELECT Menu Setup screen.