ICM Controls ICM492 Manual Download Page 1

ICM492

Single Phase Digital Line Voltage Monitor

Reliable protection of single phase systems against adverse line voltage conditions

SPECIFICATIONS

User Adjustable Settings:

• 

Voltage setpoint:

 95-280V

• 

Anti-short cycle time delay:

 0-720 sec.

• 

Over voltage setting:

 5-25%

• 

Under voltage setting:

 5-25%

• 

Control mode:

 On and Off

• 

Response time:

 0.1 to 10 seconds

Inputs:

• 

Line voltage:

 80 to 300 VAC

• 

Control voltage:

 24 to 240 VAC

• 

Frequency:

 50/60 Hz

• 

Accuracy:

 ±2% 

• 

Low power consumption:

 Max 50 mA @ 120V, 

 

Max 100 mA @ 240V 

Output:

• 

Type:

 dry relay contacts

• 

Form:

 SPDT

• 

Relay contact ratings:

 

  – 

N.C. Contacts:

 10A resistive @ 277 VAC

  – 

N.O. Contacts:

 10A resistive @ 277 VAC

• 

Connection Terminals:

 0.25” male fast-on

Mechanical:

• 

Case dimensions:

 3”L x 3.2”W x 1.35”H

• 

Unit weight:

 0.36 lbs.

Environmental:

• 

Operating temp. range:

 -30°C to +70°C

• 

Storage temp. range:

 -40°C to +85°C

• 

Maximum operating/storage relative humidity:

 

95% non-condensing

7313 William Barry Blvd., North Syracuse,  NY  13212

(Phone) 

315-233-5266

  (Toll Free) 

800-365-5525

(Fax) 

315-233-5276

www.icmcontrols.com

LII335-3

Constantly monitors and displays line 
voltage. Protects against Over and Under 
voltage, and Rapid Short Cycling caused by 
Transient Faults and Power Interruptions

The 

ICM492

 is specifically designed to monitor line 

voltage and guard single phase equipment against 
damage caused by under and over line voltage 
conditions and rapid short cycling. Records last five 
faults.

DESCRIPTION

• Universal Line Voltage 

Input

• Easy-view Backlit Digital 

Display 

• RMS Voltage Monitoring
• 5-fault memory storage
• Adjustable Voltage Set 

Point

• Adjustable Over Voltage 

Set Point

• Adjustable Under 

Voltage Set Point

FEATURES

• Adjustable Anti-Short 

Cycle Time Delay

• Adjustable Response on 

Fault Time

• Control Mode
• 5-Fault Memory
• Universal Control 

Voltage Input

• Heavy Duty SPDT Relay 

Output

The 

ICM492

 continuously monitors incoming line voltage 

for faults and displays RMS voltage on the digital 
display. When line voltage is appropriate, 

ICM492

 closes 

the COM and N.O. relay contacts. When incoming line 
voltage is outside of user selected parameters, 

ICM492

 

will close the COM and N.C. relay contacts and indicate 
a fault condition by flashing FAULT on display. The unit 
records the last five faults, storing the highest and lowest 
voltage readings that caused the fault. The UP, DOWN 
and SELECT buttons are pressed simultaneously to 
clear the faults from memory. The SELECT menu has 
the following user adjustable settings: voltage set point, 
time delay, over voltage percentage, under voltage 
percentage, control mode, and response time. Time 
delay prevents short cycling when fault no longer is 
present and rapid power interruptions. The response 
time on the fault condition can be adjusted to help 
reduce nuisance trips from transient faults. When 
Control Mode setting is selected ON then ICM492 will 
close COM and N.O. relay contacts only when control 
voltage is present at Control Voltage terminals and the 
line voltage is good. The relay contacts can be used 
to direct drive the load as long as current rating is not 
exceeded. 

MODE OF OPERATION

!!! WARNING !!!

Electrical Shock Hazard

• Verify power is disconnected by removing a fuse 

or opening a circuit breaker before making any 
connections.

• This control should be installed by a trained technician.

• Incorrect installation can cause personal injuries, 

property damage or death.

• Follow all local & national codes while installing control.