background image

1.  Press the SETUP button to enter Setup mode. Setup LED will light. 
2.  Use the   and   arrows to change user parameters.
3.  Scroll through setup by pressing and releasing the SETUP button.
4.  When the last parameter has been set, the phase average will be displayed and the 

Setup LED will automatically turn OFF.

Setting the Parameters

Button Functions

Press arrows to scroll 

through and select user 

parameter settings in 

Setup mode. HOLD 

down for fast edit.

Press to 

enter Setup 

mode and 

select user 

parameters.

Hold for 

voltage display

a   b, b   c, 

a   c

(simultaneously).

Press to read 

faults. Hold for 5 

seconds to clear 

faults and reset 

memory.

Installation

1.  Using (2) #8 screws, mount the ICM450A and ICM450A plus+ in a cool, dry, easily 

accessible location in the control panel.

2. Connect voltage as shown in Figure 1 (below). Leave existing line and load side 

connections intact on the contactor.

3. Load side monitoring is optional (unit may be used to monitor line side only). Wire the 

contactor and optional control voltage monitoring as in Figures 2 and 3 (below). 

 

 Note: Load/line wire must be rated for 3-phase voltage rating, 20 AWG minimum.

4. Upon application of power, the CM450A and ICM450A plus+ will be on line and will 

begin to monitor the system.

•  Terminals 4 and 5 are the control signal input terminals
•  “Control Mode” is turned ON or OFF in setup
•  With “Control Mode” set to “ON,” there must be a voltage present on terminals 4 and 

5 for the relay output terminals 1 and 2 to close; this voltage can be supplied from a 

thermostat, pressure switch, etc.

•  When the voltage on these terminals is re-applied,  

the unit will not re-energize until the delay on break  

(0-10 minutes) time has elapsed

•  Use of terminals 4 and 5 is optional; they will be ignored if the “Control Mode” is 

set to “OFF”

•  Terminals 1 and 2 are “dry,” normally open contacts
•  Terminals 1 and 2 are closed when power is within specifications
•  Terminals 1 and 2 open when there is a fault condition
•  Terminals 1 and 2 open when there is a loss of the control signal with “Control Mode” set 

to “ON”

 Note: Terminals 6, 7 and 8 used for ModBus communication on ICM450A and 

ICM450A plus+.

Figure 3

Contactor Voltage 

(18-240 VAC)

Optional Control Voltage

Contactor 

Coil

COM NO NC

Figure 2

Contactor Voltage 

(18-240 VAC)

Optional Control Voltage

Contactor 

Coil

COM NO NC

Figure 1

Incoming 3-phase 

voltage from load

or “back” side of 

contactor (optional)

Incoming 3-phase voltage from 

line or “front” side of contactor

The incoming 3-phase voltage 

is used to power up the 

ICM450A as well (190-600)

ICM450A and ICM450A plus+ Wiring Diagrams

Load 3

Load 2

Load 1

LOAD

L1 L2

3-Pole Contactor

Load 2

Load 1

L1 L2

2-Pole Contactor

Load 

3

LOAD

L3

L3

6

8

7

4

3

2

5

1

Optional Control 

Voltage

18-240 VAC

6

8

7

4

3

2

5

1

Optional Control 

Voltage

18-240 VAC

ICM450A & 
ICM450A plus+

Programmable 3-Phase 
Line Voltage Monitors

Installation of the ICM450A and ICM450A plus+ shall be performed by trained 

technicians only. Adhere to all local and national electric codes. 
Disconnect all power to the system before making any connections.

Caution

Specification

Input

• Line Voltage: Universal, 190-600 VAC

• Frequency: 50-60 Hz

• Load Side Monitoring: Optional

• Control Voltage: 18-240 VAC

• Frequency: 50-60 Hz
Output

• Type: Relay, SPDT

• Voltage Range: 277 VAC @ 10A maximum

• Frequency: 50-60 Hz
Control Operating Temperature

•  Operating Temperature: -40ºF to +167ºF (-40ºC to +75ºC)

•  Storage Temperature: -40ºF to +185ºF (-40ºC to +80ºC)
LCD Operating Temperature : -4ºF to +167ºF (-20ºC to +75ºC)

Mechanical:

• Mounting: Surface mount using (2) #8 screws

• Terminations: 1/4” quick connects

• Weight: 12 ounces (341 grams)
ModBus: RS485 Communication (ICM450A plus+)
Dimensions: 6.5”L x 4.75”W x 1.09”D

Parameters

Line Voltage: Universal 190-600 VAC
Phase Unbalance Protection

•  Voltage Unbalance: 2-20% adjustable
Over/Under Voltage Protection

•  Under Voltage: 2-25% adjustable

•  Over Voltage: 2-25% adjustable
Phase Loss Protection

•  Phase Loss Condition:  Equals 25% of nominal for any given phase; system will shut 

down and a fault will be recorded should this occur

Delay on Break Timer

•  Time Delay: 0 to 10 minutes adjustable
Control Voltage: 18-240 VAC

•  Control Mode: ON/OFF
Fault Interrogation Delay

•  Time Delay: 0 to 15 seconds adjustable

•  Provides a delay between fault detection and system shutdown - helps to eliminate 

nuisance trips or unnecessary shutdowns

Reset Mode: 0 (auto) or 1-10 retries
Set Date and Time: Provides real time clock for date and time stamp (ICM450A plus+)
Language: Set to English or Spanish language for display