ICM Controls ICM326HN General Installation, Operation And Maintenance Instructions Download Page 1

ICM326HN / ICM327HN

Line Voltage Head Pressure Control

With built-in transformer Optional heat pump override

ICM326HN

ICM327HN

• 

Line voltage:

 120, 208/240, and 480 VAC

• 

Frequency:

 50-60 Hz

• 

Output:

 10 amp maximum, 100 mA minimum

• 

Operating temperature:

 -40ºF to +176ºF (-40°C to +75°C)

• 

Sensors:

 10K ohms at 25°C

• 

Heat pump override:

 N.C. or N.O.

 

 

Note:

 

A maximum of three sensors can be connected to the control

• 

Weight:

 12 ounces (341 grams)

 

 

Note:

 

The ICM326HN and ICM327HN should be applied to motors and equipment that have been designated 
by their respective manufacturers as capable of being speed controlled

• 

Mounting:

 

  –  Surface mount using (4) #8 screws
  –  The 

ICM326HN

 and 

ICM327HN

 should be surface mounted to a clean metal or other thermally-conductive 

surface for maximum heat dissipation

  –  It is recommended that the 

ICM326HN

 and 

ICM327HN

 be mounted away from the condenser exhaust air to 

maintain lower operating temperatures

ELECTRICAL SHOCK HAZARD –

 

Installation of the 

ICM326HN

 and 

ICM327HN

 shall be performed by 

trained technicians only. Adhere to all local and national electric codes. Disconnect all power to the system 
before making connections.

Specifications

Installation of the ICM326HN and ICM327HN shall be performed by trained technicians only. Adhere to all 
local and national electric codes. 

Disconnect all power to the system before making any connections.

Caution!

Connecting the Probe

Example

1.  Install the temperature probe several bends into the condenser. It can be attached to the 

U-bend or placed between the fins in the upper 1/3 of the condenser (see other side for 
more information).

 

 

Note:

 

The response of the system can be fine tuned by repositioning the probe. Place 
the probe on the condenser where it is 100°F when pressures are correct for 
best response.

2.  Connect the two wires from the sensor to the terminal block where it is marked 

PROBE S1

If additional probes are necessary for multiple refrigerant circuits, they may be attached to 
terminals marked 

PROBE S2

 and 

PROBE S3

.

 

 

Note:

 

The control will respond to the probe that senses the highest temperature.

Connections for Heat Pump System at 480 VAC

1. Remove power from system.
2. Field install a wire from 

Line 1

 wire to 

Line 1

 terminal.

3. Cut 

Line 2

 wire; affix the common from the defrost 

board’s fan relay to the 

Motor 2

 terminal and the Line 

from the contactor to the 

Line 2

 terminal.

4. Make 24 VAC, probe and HP connections.
5. Verify wiring is correct.
6. Power up system and check operation.

Line

1

480 VAC

Line

2

Motor

2

480 VAC

Field  

Installed 

Wire

PSC 

Fan 

Motor

Run  

Capacitor

Fan 

Relay

COM

NC

Defrost Board

Connections for Air Conditioning Only

1. 

For non-heat pump applications

, the heat 

pump select jumper must be in the 

Default

 

(

N.O.

) position, and the HP terminals must be left 

unconnected.

Heat Pump 

Select Jumper 

Default Position

Probe S1

Probe S2

Probe S3

HP

Temperature 

Probe

1. Remove power from system.
2. Field install a wire from 

Line 1

 wire to 

Line 1

 terminal.

3. Cut 

Line 2

 wire; affix motor side to 

Motor 2

 terminal 

and line side to 

Line 2

 terminal.

4. Make 24 VAC and temperature probe connections.
5. Verify wiring is correct.
6. Power up system and check operation.

Typical 
condenser fan

PSC 

Fan 

Motor

Run 

Capacitor

120 VAC

PSC 

Fan 

Motor

Run  

Capacitor

Field  

Installed 

Wire

Line

1

120 VAC

Line

2

Motor

2

120 VAC

Connections for ICM327HN at 480 VAC

1. Remove power from system.
2. Field install a wire from 

Line 1

 wire to 

Line 1

 terminal.

3. Cut 

Line 2

 wire; affix motor side to 

Motor 2

 terminal 

and line side to 

Line 2

 terminal.

4. Make 24 VAC and temperature probe connections.
5. Verify wiring is correct.
6. Power up system and check operation.

Line

1

480 VAC

Line

2

Motor

2

480 VAC

Field  

Installed 

Wire

PSC 

Fan 

Motor

Run  

Capacitor

Typical 
condenser fan

PSC 

Fan 

Motor

Run 

Capacitor

Field  

Installed 

Wire

PSC 

Fan 

Motor

Run  

Capacitor

Fan 

Relay

COM

NC

Defrost Board

208/240

VAC

Line

1

240 VAC 

Line

2

Motor

2

Connections for Heat Pump System at 208/240 VAC

1. Remove power from system.
2. Field install a wire from 

Line 1

 wire to 

Line 1

 terminal.

3. Cut 

Line 2

 wire; affix the common from the defrost 

board’s fan relay to the 

Motor 2

 terminal and the Line 

from the contactor to the 

Line 2

 terminal.

4. Make 24 VAC, probe and HP connections.
5. Verify wiring is correct.
6. Power up system and check operation.

Connections for Heat Pump Systems

 

 

Note:

 

HP terminals will not recognize 24 VAC. Line voltage must be applied (120, 208/240, or 480 VAC).

1.  The heat pump terminals accept the line voltage signal from the reversing valve holding coil. Make a parallel 

connection from the reversing valve to HP terminals.

2.  If the heat pump is in the 

Heating

 mode and the reversing valve is energized, then the 

Heat Pump 

Select

 jumper must be in the 

Default

 (

N.O.

) position.

3.  If the heat pump is in the 

Heating

 mode and the reversing valve is 

not

 energized, then the 

Heat 

Pump Select

 jumper must be in the 

N.C.

 position.

N.O.

N.C.

Connect Parallel to 

Reversing Valve

Heat Pump 

Select Jumper 

Default Position

Probe S1

Probe S2

Probe S3

HP

Temperature 

Probe

RV

Connections for ICM326HN at 120 VAC