ICM326HN / ICM327HN
Line Voltage Head Pressure Control
With built-in transformer Optional heat pump override
ICM326HN
ICM327HN
•
Line voltage:
120, 208/240, and 480 VAC
•
Frequency:
50-60 Hz
•
Output:
10 amp maximum, 100 mA minimum
•
Operating temperature:
-40ºF to +176ºF (-40°C to +75°C)
•
Sensors:
10K ohms at 25°C
•
Heat pump override:
N.C. or N.O.
Note:
A maximum of three sensors can be connected to the control
•
Weight:
12 ounces (341 grams)
Note:
The ICM326HN and ICM327HN should be applied to motors and equipment that have been designated
by their respective manufacturers as capable of being speed controlled
•
Mounting:
– Surface mount using (4) #8 screws
– The
ICM326HN
and
ICM327HN
should be surface mounted to a clean metal or other thermally-conductive
surface for maximum heat dissipation
– It is recommended that the
ICM326HN
and
ICM327HN
be mounted away from the condenser exhaust air to
maintain lower operating temperatures
ELECTRICAL SHOCK HAZARD –
Installation of the
ICM326HN
and
ICM327HN
shall be performed by
trained technicians only. Adhere to all local and national electric codes. Disconnect all power to the system
before making connections.
Specifications
Installation of the ICM326HN and ICM327HN shall be performed by trained technicians only. Adhere to all
local and national electric codes.
Disconnect all power to the system before making any connections.
Caution!
Connecting the Probe
Example
1. Install the temperature probe several bends into the condenser. It can be attached to the
U-bend or placed between the fins in the upper 1/3 of the condenser (see other side for
more information).
Note:
The response of the system can be fine tuned by repositioning the probe. Place
the probe on the condenser where it is 100°F when pressures are correct for
best response.
2. Connect the two wires from the sensor to the terminal block where it is marked
PROBE S1
.
If additional probes are necessary for multiple refrigerant circuits, they may be attached to
terminals marked
PROBE S2
and
PROBE S3
.
Note:
The control will respond to the probe that senses the highest temperature.
Connections for Heat Pump System at 480 VAC
1. Remove power from system.
2. Field install a wire from
Line 1
wire to
Line 1
terminal.
3. Cut
Line 2
wire; affix the common from the defrost
board’s fan relay to the
Motor 2
terminal and the Line
from the contactor to the
Line 2
terminal.
4. Make 24 VAC, probe and HP connections.
5. Verify wiring is correct.
6. Power up system and check operation.
Line
1
480 VAC
Line
2
Motor
2
480 VAC
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM
NC
Defrost Board
Connections for Air Conditioning Only
1.
For non-heat pump applications
, the heat
pump select jumper must be in the
Default
(
N.O.
) position, and the HP terminals must be left
unconnected.
Heat Pump
Select Jumper
Default Position
Probe S1
Probe S2
Probe S3
HP
Temperature
Probe
1. Remove power from system.
2. Field install a wire from
Line 1
wire to
Line 1
terminal.
3. Cut
Line 2
wire; affix motor side to
Motor 2
terminal
and line side to
Line 2
terminal.
4. Make 24 VAC and temperature probe connections.
5. Verify wiring is correct.
6. Power up system and check operation.
Typical
condenser fan
PSC
Fan
Motor
Run
Capacitor
120 VAC
PSC
Fan
Motor
Run
Capacitor
Field
Installed
Wire
Line
1
120 VAC
Line
2
Motor
2
120 VAC
Connections for ICM327HN at 480 VAC
1. Remove power from system.
2. Field install a wire from
Line 1
wire to
Line 1
terminal.
3. Cut
Line 2
wire; affix motor side to
Motor 2
terminal
and line side to
Line 2
terminal.
4. Make 24 VAC and temperature probe connections.
5. Verify wiring is correct.
6. Power up system and check operation.
Line
1
480 VAC
Line
2
Motor
2
480 VAC
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Typical
condenser fan
PSC
Fan
Motor
Run
Capacitor
Field
Installed
Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM
NC
Defrost Board
208/240
VAC
Line
1
240 VAC
Line
2
Motor
2
Connections for Heat Pump System at 208/240 VAC
1. Remove power from system.
2. Field install a wire from
Line 1
wire to
Line 1
terminal.
3. Cut
Line 2
wire; affix the common from the defrost
board’s fan relay to the
Motor 2
terminal and the Line
from the contactor to the
Line 2
terminal.
4. Make 24 VAC, probe and HP connections.
5. Verify wiring is correct.
6. Power up system and check operation.
Connections for Heat Pump Systems
Note:
HP terminals will not recognize 24 VAC. Line voltage must be applied (120, 208/240, or 480 VAC).
1. The heat pump terminals accept the line voltage signal from the reversing valve holding coil. Make a parallel
connection from the reversing valve to HP terminals.
2. If the heat pump is in the
Heating
mode and the reversing valve is energized, then the
Heat Pump
Select
jumper must be in the
Default
(
N.O.
) position.
3. If the heat pump is in the
Heating
mode and the reversing valve is
not
energized, then the
Heat
Pump Select
jumper must be in the
N.C.
position.
N.O.
N.C.
Connect Parallel to
Reversing Valve
Heat Pump
Select Jumper
Default Position
Probe S1
Probe S2
Probe S3
HP
Temperature
Probe
RV
Connections for ICM326HN at 120 VAC