Models:
ICM P/N
Lockout
Timing*
(seconds)
Valve-on
Delay
(seconds)
Burner
Motor-off Delay
(minutes)
Alarm
Contacts
Thermostat
JW5
Limit
JW1
ICM1511*
Factory Set
15, 30 or 45
Selectable
0 or 15
Selectable 0
or 0, 2, 4, 6 (b)
YES
NO
NO
ICM1512*
15
0, 2, 4, 6 (b) or
0.5, 2, 4, or 8
OPTIONAL
NO
NO
ICM1513*
15
NONE
NONE
YES(a)
YES
ICM1514*
NONE
NONE
NONE
YES
YES
Notes:
• Factory default is
15 seconds
.
• For
30 second
safety timing, add “
A
” to the end of the ICM part number (i.e.: ICM1511A)
• For
45 second
safety timing, add “
B
” to the end of the ICM part number (i.e.: ICM1511B)
Specifications
Timing:
•
Safe start check:
5 seconds (approximate)
•
Valve-on delay:
Model dependent; see chart above
•
Burner motor-off delay:
Model dependent; see chart above
•
Lockout:
15, 30 or 45 seconds (factory-programmed)
•
Recycle:
60 seconds (fixed)
•
Ignition carryover:
10 seconds (fixed)
• DIP switch positions 1 and 2 are to set burner motor-off delay timings
• DIP switch position 3 is to enable or disable valve on delay timing
Table 1