General information
9
ASX 200 ÷ 800(12 BAR)
DESCRIPTION
u.m.
ASX
200
300
400
500
600
800
Nominal power
kW
233
349
465
581
698
930
Thermal capacity
kW
258
387
516
645
774
1032
Efficiency at 100% (N.C.V.)
%
90,31
90,18
90,12
90,08
90,18
90,12
Hydraulic pressure drop
mbar
30
29
22
33
48
22
Rated pressure
bar
5
5
5
5
5
5
Total capacity
l
730
735
825
1080
1250
1515
Total weight
kg
1540
1580
2035
2925
3245
3600
Electric supply
Volt ~
230
230
230
230
230
230
Frequency
Hz
50
50
50
50
50
50
Insulation class
IP
IP55
IP55
IP55
IP55
IP55
IP55
Electric power
W
W.D.
W.D.
W.D.
W.D.
W.D.
W.D.
Allowed fuels
Methane - LPG - Diesel - Naphtha
ASX 1000 ÷ 3000(12 BAR)
DESCRIPTION
u.m.
ASX
1000
1200
1500
1750
2000
2500
3000
Nominal power
kW
1163
1395
1744
2035
2326
2907
3488
Thermal capacity
kW
1292
1550
1959
2260
2584
3229
3876
Efficiency at 100% (N.C.V.)
%
90,02
90,00
89,03
90,04
90,02
90,03
89,99
Hydraulic pressure drop
mbar
54
78
59
80
105
52
75
Rated pressure
bar
12
12
12
12
12
12
12
Total capacity
l
1705
2265
2835
3135
3560
4360
5170
Total weight
kg
4150
4510
5460
6000
8800
9600
10650
Electric supply
Volt ~
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
Frequency
Hz
50
50
50
50
50
50
50
Insulation class
IP
IP55
IP55
IP55
IP55
IP55
IP55
IP55
Electric power
W
W.D.
1000
1000
1000
1000
1000
1000
Allowed fuels
Methane - LPG - Diesel - Naphtha
Water delivery ΔT max 30°C.
Electric powers only for gas or diesel fuels.
Design data
Minimum/maximum temperature
-10°C / 158,9 °C
Minimum/maximum temperature
-10°C / 191,7 °C
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz