6
The
RCA
remote condensers incorporate the mixing valve in the condenser. This configuration allows up to
a 100 foot calculated remote line set run.
The
RGA
remote condensers
Do Not
have a mixing valve in the condenser.
Maximum Rise is 35 feet
Maximum Drop is 10 feet.
Maximum equivalent run is 100 feet
.
Formula for calculating maximum equivalent run is as follows:
Rise x 1.7 + Drop x 6.6 + horizontal run = equivalent run
Example:
35 ft. rise x 1.7 + 40 ft. horizontal = 99.5 ft. equivalent line run
Example
: 10 ft. drop x 6.6 + 34 ft. horizontal = 100 ft. equivalent line run
Airflow
Airflow
35 ft. rise
40 ft. horizontal
10 ft. drop
34 ft. horizontal