background image

OPERATING & MAINTENANCE MANUAL

 – 

CONSOLE HYBRID WATER-COOLED AIR CONDITIONER (CHW)

8

FILTER

ICE AIR WCACs

 are equipped with a washable/reusable 

Aluminum Filter.  It is recommended that you clean the indoor 
air filter after every 350 to 400 hours of unit operation – more 
frequently if the unit is running in an environment of high dust, 
pet dander or other pollutants in the indoor atmosphere. 

• 

Filter inspection: The filter is located at 

 

the bottom of your unit. To remove filter, 

 

slide it out towards you. 

• 

To reinstall, place filter under the unit  

 

and slide back into the filter rack.

FILTER CLEANING 

To clean your filter, use lukewarm water with a biodegradable 
cleaner. Rinse and allow to dry completely before reinstall-
ing in unit. (As an alternate cleaning method, the filter may 
be cleaned on both sides using a vacuum cleaner with a soft 
brush type attachment).

DO NOT OPERATE UNIT WITHOUT FILTER.

 

This practice will damage and/or seriously impair  
the performance of your unit and could void your Warranty.

ROOMSIDE COMPONENT CLEANING

Evaporator Coil and Drain Pan / Drain Hoses

IMPORTANT NOTE:  The power MUST be disconnected to the 
unit before carrying out any of the following cleaning!

To access the components within the roomside section of 
the unit, disconnect the power to the unit and then remove 
the unit chassis front cover by unscrewing the #8 hex head 
retaining screws that hold the front cover in place (use a ¼” 
hex head driver). You will then have access to the following 
components: 

EVAPORATOR COIL 

Check the coil for cleanliness and uniformity of fins. If the 
coil is dirty, vacuum clean with a soft brush attachment. 
This is the only form of cleaning that should be carried 
out within an apartment. If the coil requires additional 
cleaning, the unit must be removed from the apartment 
and cleaned using compressed air and / or washed. 
These operations MUST be carried out in a facility prop-
erly equipped to handle this type of work in a safe and 
professional manner. 

DRAIN PAN / DRAIN HOSE CLEANING

The condensate pan is located directly under the  
evaporator coil. Check the visible section of the interior of 
the drain pan for any buildup of dirt or condensate water. 
Wash annually to remove all dirt build-up. Check 
condensate drain pan for algae growth every 2 to 3 
months.  If algae growth is apparent, consult a water 
treatment specialist for treatment. The application of 
algaecide every 2 to 3 months will typically eliminate 
algae problems. 

DRAIN HOSE

Check drain hose for leaks and blockage to eliminate 
potential problems.

Summary of Contents for CHW

Page 1: ...Console Hybrid Water Cooled Air Conditioner CHW OPERATING MAINTENANCE MANUAL World Class Comfort ...

Page 2: ...BS FINISH N A DRAWING BY DATE TITLE SIZE DWG NO REV SCALE NONE UNLESS OTHERWISE SPECIFIED SHEET 1 OF 1 DO NOT SCALE DRAWING HYBRID C WSHP WITH SLIDING CHASSIS CABINET GENERAL ASS Y DIMENSIONS ARE IN INCHES TOLERANCES FRACTIONAL 1 32 ANGULAR MACH BEND 1 TWO PLACE DECIMAL 03 THREE PLACE DECIMAL 015 This drawing is the intellectual property of Ice Air LLC and consists of confidential data belonging s...

Page 3: ...y will be explained in a separate instruction sheet specific to that option On behalf of ICE AIR and our network of distributors and dealers we are happy to welcome you to our base of satisfied customers CONSUMER SAFETY AND OPERATING NOTES FOR SAFE AND OPTIMAL ENJOYMENT OF YOUR ICE AIR CHW UNIT PLEASE READ THE FOLLOWING CONSUMER SAFETY AND OPERATING NOTES CAREFULLY BEFORE OPERATING YOUR EQUIPMENT ...

Page 4: ...tions must be maintained for proper unit operation Unobstructed air flow into and out of the unit room enclosure cabinet Therefore Do not place furniture rugs or objects directly in front of underneath or against the unit cabinet front Do not place plants fabrics or objects on top of or blocking the enclosure discharge grille at the cabinet top Do not block the top of the cabinet with drapes or cu...

Page 5: ...own Permanent over ride mode ON OFF ON OFF MODE Set operation mode Internal Setting FAN Set fan speed Confirm USER INTERFACE PUSH BUTTONS Operation Normal Mode 1 Press ON OFF to turn on thermostat 2 Press Mode to change the system mode 3 There are three operation modes Cool Mode Heat Mode Auto Mode Cool Mode To activate cooling mode press the mode button until COOL displays Press up down arrow key...

Page 6: ...t limit setting The cool limit setting is 55 F to 95 F The heat limit setting is 51 F to 91 F Exit Internal Setting and Return to Normal Mode 1 Press Fan to confirm and return to normal mode 2 If no key is pressed for 15 seconds it will return to normal mode automatically Auto Mode To activate auto mode press the mode button until AUTO displays Press up down arrow keys to set desired heat temperat...

Page 7: ... 95 F Resolution 0 5 C 1 F Operating temperature 0 50 C 32 122 F Storage temperature 5 50 C 23 122 F MAINTENANCE SERVICE CAUTION to prevent injury or death due to electrical shock or contact with moving part turn off the disconnect switch before servicing this unit IMPORTANT NOTE It is not the intent of this maintenance manual to correct any installation deficiencies If you have any doubt about th...

Page 8: ...ollowing cleaning To access the components within the roomside section of the unit disconnect the power to the unit and then remove the unit chassis front cover by unscrewing the 8 hex head retaining screws that hold the front cover in place use a hex head driver You will then have access to the following components EVAPORATOR COIL Check the coil for cleanliness and uniformity of fins If the coil ...

Page 9: ...tem with water problem history it is best to establish a periodic maintenance program It is the building s responsibility to maintain a water system that should provide your unit with treated and filtered water to keep water flowing freely through your equipment Generally if the water flow exceeds 3 gpm per tonthe water elocities should keep your coil free of scaling and debris that could lead to ...

Page 10: ...te Look for wiring errors Check for loose screw connections in both line and low voltage terminals Check the water supply piping for proper water connection Check for dirty filters Check indoor fan for proper operation Check that unit did not cycle off on thermostat Check for fault codes on the control board consult the trouble shooting guide 2 If checks above fail to reveal operating problem and ...

Page 11: ... ICE AIR INSTALLATION MANUAL AND PROCEDURES MUST BE SERVICED BY QUALIFIED TRAINED PERSONNEL ELECTRIC SHOCK HAZARD DISCONNECT FROM LIVE ELECTRIC CIRCUIT BEFORE SERVICING MOVING PARTS HAZARD DISCONNECT FROM LIVE ELECTRIC CIRCUIT BEFORE SERVICING UNIT MUST BE OPERATED WITH ALL CHASSIS SHEET METAL PARTS PROPERLY IN PLACE UNIT MUST BE OPERATED WITH ALL ENCLOSURE CABINET PARTS IN PLACE READ THIS ENTIRE ...

Reviews: