Ph value
(
25
℃
)
6.5 − 8.0
Chloridion
(
CL
)
(
mg/L
)
<
50
Conductivity
(
25
℃
)
(
μs/cm)
<
250
Silver sulfate
(
SO42
−
)
(
mg/L
)
<
50
Total iron
(
mg/L
)
<
0.3
Total alkalinity
<
50
Total hardness
(
mg/L
)
<
50
Silicon dioxide
(
SiO2
)
<
30
5. Water system piping for atmospheric (open) tank
6. Winter freeze protection
The unit is equipped with a freeze protection program. If the unit has power and senses the water is
below 40°F, it will turn on and operate the system until the water is at 60°F. To protect the hydronic
components from freezing during a power outage, there are a few options.
Option 1
: Order the unit with factory mounted heat-trace and connect the heat-trace circuit to the
building emergency power supply.
Option 2
: Utilize a glycol loop for the outdoor hydronic components; and a secondary double wall
heat exchanger between the glycol loop and potable hot water located indoors.
Option 3:
Drain the system during ambient conditions at or below 32°F (0
℃
). To properly drain the
system, follow the steps noted below: