ICC
81
Figure 67: MSG Configuration, "General" Tab
c)
In this example, we will be reading a total of 25 function codes beginning at N30:50 (register
2050 / function code M01). To configure this, under “This Controller” set the “Data Table
Address” field to N18:1, set the “Size in Elements field” to 25, and set the “Channel” field to 1
(Ethernet).
d)
Under “Target Device”, set the “Data Table Address” field to N30:50 (starting target
register=2050) and set the “MultiHop” field to Yes to cause the “MultiHop” tab to appear.
e)
Under the “MultiHop” tab settings, set the “To Address” in the first row to the inverter’s IP
address, and the “To Address” in the second row to 0. Refer to Figure 68.
Figure 68: MSG Configuration, "MultiHop" Tab
f)
Close the dialog box. At this point, the program should appear as shown in Figure 69.