DEVICE CONFIGURATIONS
ETH-1000 WIRING
shows the standard configuration of the Ethernet modules.
The module has connections for 9 VDC power, three wire
connections for the communication cable, and a port for the
connection of the EMS system through Ethernet RJ-45 cable or
serial communications.
Figure 6.
Standard Configuration for Ethernet Modules
Connecting of the power adapter and the boiler or water heater
communication cable to the module is accomplished on the same
end of the unit.
is a close up of the connection terminal
shows the appropriate connection to the strip using
the power adapter and communication cable.
The provided communication cable has two RJ-45 plugs.
Remove one with a wire cutter, then locate and strip the 3 wires
described below and strip 1/2 inch of insulation before connecting.
Figure 7. Connecting the Power Adapter
Brown/White Wire*
Jumper
Brown Wire*
Blue/White Wire*
Black/White Wire
†
Black Wire
†
*From Communication Cable
†
From 9 VDC Power Adapter Cable
RS 485
A
B
Y
Z
Power
GND
Power
Pos
Jumper
Figure 8. Connections from the Communications and Power Adapter Cables
are the same regardless of the
appliance or the communication protocol.
At the opposite end of the module is the connection location for
the EMS LAN connection. The EMS uses an Ethernet connection
with an RJ-45 connector. Plug the cable into the RJ-45 receptacle.
When connecting the RS-485A connections, please note the
following:
For 2-wire systems, jumper terminal A to Y. Also jumper B to Z.
Connect the RX/TX+ (plus) wire from your Building Management
System to terminal A/Y. Connect the RX/TX– (minus) wire from
your Building Management System to terminal B/Z.
For more information on connecting the ICC Gateway to your
Building Management System, please refer to the User Manual
provided on the enclosed USB key in the “Documents” folder. The
two applicable documents will be found in the Manuals.
MIRIUS WIRING
shows the he standard configuration of the module. Port A
of the module has connections for 9 VDC power, three wire
connections for the communication (breakout) cable, for Serial
communications to the water heater/boiler.
is a close up of the connection terminal and
shows the appropriate connection to the strip using the power
adapter and communication cable.
Summary of Contents for Mirius
Page 54: ...54 NOTES...
Page 55: ...55 NOTES...