VIII. TROUBLE SHOOTING /
PETUNJUK KETIDAK
NORMALAN
SYMPTOM
PROBABLE CAUSE
RECOMMENDED
SOLUTION
Inverter indicator is not
light on.
Inverter not running.
Turn off main switch, and turn on
main switch again.
1. Remove some load from the INV.
2. If it remains the same, call for
service.
1. Turn off main switch and turn on
main switch again.
2. If doesn’t recover, call for service.
If DC input voltage/ Battery > 99V,
call for service.
If DC input voltage/ Battery > 99V
or <130.5V, call for service.
Overload.
Inverter not running.
DC input voltage low or
Battery low <99V.
1. Inverter not running.
2. DC input voltage/
battery <99V or
>130.5V.
Overload and fault
indicator are on, but alarm
sounds.
Fault indicator is on, and
alarm sounds
continuously.
Inverter on and alarm
sounds every 1 second.
No output voltage when
turn on the main switch
“ON”.
KEJADIAN
KEMUNGKINAN
PENYEBAB
REKOMENDASI
SOLUSI
Indikator inverter tidak
menyala.
Inverter tidak bekerja.
Matikan main Switch, lalu coba
hidupkan sekali lagi.
1. Lepas sebagian beban dari INV.
2. Jika tidak ada perubahan, hubungi
service centre.
1. Matikan main Switch, lalu coba
hidupkan sekali lagi.
2. Jika keadaan tetap, hubungi
service centre.
Bila tegangan input DC/ Baterai
>99V, hubungi service centre.
Bila tegangan input DC/ Baterai
>99V atau <130.5V, hubungi service
centre.
Beban lebih.
Inverter tidak bekerja.
Tegangan input DC/
Baterai rendah.
1. Inverter tidak bekerja.
2. Tegangan input DC/
Baterai <99V atau
>130.5V.
Indikator Overload dan
Fault menyala dan buzzer
berbunyi panjang.
Indikator Fault menyala,
buzzer berbunyi panjang.
Iindikator Inverter On
menyala dan buzzer
berbunyi cepat.
Tidak ada tegangan output
setelah Switch ON
ditekan.
5