2.

 

 if using a self-suction centrifugal pump valve must be installed at the pump outlet and switch should 
be installed> 1 m above the valve to the pressure switch was stable. 

3.

 

Note if the source water is above the level of the suction nozzle of the pump and the water pump is 
supplied to gravity, set the pressure switch L, less than 2 bars and is a pump having a low working 
pressure, in order to prevent frequent on / off switching of the pump which affects its service life. 

 

4.

 

DESCRIPTION OF FUNCTIONS 

 
 ❶ ❷ ❸ ❹  
 

In order to avoid frequent switching on and off the pump, set the delay off the pump. In order to set the delay 
simultaneously press two keys (1 and 2 above) and hold for three seconds, the display shows "n03" (n is the 
number of the delay is 3 seconds) using the above button no. 2 and 3 to modify the time. If no operation is 
performed within 3 seconds, the setting is automatically saved and the unit will go into operation. 

 

Dry-running protection 
 

Protection against dry-running is enabled by default if a specific reason you do not want to leave this feature 
turned on, simultaneously press the No. 2 and No. 4 and hold for 3 seconds, the display will show the code "F0" 
(function off) or F1 ( function enabled by default) if no operation is performed within 3 seconds, it will 
automatically save and return to operating mode. 

 

5.

 

TROUBLESHOOTING 

Tabela.2

 

Problem 

possible cause 

Solution 

 
 

The valve was closed 

and the pump 

continues to work 

No suction power, the water level dropped below 

7m. 

Lower the pump mounting location 

Switch-off pressure (H) is set too high, the pump can 

not reach the required pressure. 

Lower pressure means (H) below 

wilskości shown on the display while 

the valve is closed. 

No valve, the water backs up in the pipeline. 

Install the valve 

 

The suction pressure in the suction pipe is not 

higher pressure switch (L) 

Increase the pressure switch (L) 

 

DECLARATION OF CONFORMITY EC / EU (Module A): 

 

1.

 

Pressure switches: 10P-PC, PC-14, PC-15, PC-16, PC-59, SK-15, LCI2, SK2-PC, PC-2, 1 DIGIBO 

2.

 

PHU Dambat, Gawartowa Wola 38, 05-085 KAMPINOS, POLAND e-mail: [email protected] 

3.

 

This declaration of conformity is issued under the sole responsibility of the manufacturer. 

4.

 

Series of switches contained in the Step 1. 

5.

 

On the basis of the Act of 30 August 2002. A compliance system (Journal of Laws of 2004. No. 204, item. 2087) 
declare with full responsibility that the submersible pump to which this declaration relates, are made in accordance 
with the following directives and they included references to the following standards: 

 

LVD Directive no. 2014/35 / EU 

 

EMC Directive No. 2014/30 / EU 

6.

 

Applied standards: 

EN 60730-1: 2002, EN 61000-6-1: 2007, EN 61000-6-2: 2007,   
EN 61000-6-3: 2007, EN 61000-6-4: 2007 