IBO DIGIBO 1 User Manual Download Page 1

 

USER MANUAL 

SMART PRESSURE SWITCH TO PUMP 

DIGIBO 1

 

 

 

1.

 

 TECHNICAL DATA 

Table 1. Recommended settings depending on the parameters

 

 

Range: 0-10 bar 
Power supply: 230V, 50Hz

 

Protection: IP66 
The maximum pump power: 1.5 kW 
Maximum temperature: 80 ° C 
Warranty: 2 years / 20 million cycles 

  

 Upper limit = (H max) / 10 - (0.4 or 0.5)

 

Installation: 

 

1 If the pump does not have a check valve, pressure switch before you need to install a check valve to prevent 
backflow of water that make the switch will not work properly in this case the pump can be switched off 
naprzemiennie.2. After unscrewing the tap / valve, if the pump is alternately turned on / off, set a higher value 
H. 
3. If the pump is still operating despite the closure of the valve, reduce the value H, while if the pump does not 
turn, set a higher value L.  

 

2.

 

SETTING THE PARAMETERS 
 

Setting the pressure off - H 

 

Use the buttons (arrow keys) to set a limit, up arrow - to increase, down arrow - to decrease, after setting the 
switch to save the settings and automatically switches to the operation mode. 

1.

 

 to set a relatively high value H, e.g.,. H5,5 

2.

 

 close all valves and check the value on the display, for example. 4.5 

3.

 

open the upper valve, and turn on the pump, the pump draws water smoothly, check the value on the 
display, for example. 3,5. 

4.

 

 This means that the actual value should be 3.5-4.5 H, normally set to a value of 0.3 or 0.4 below the last 
proven value in this case is H - 4.1. 

5.

 

the maximum operating pressure of the pump is usually (max. Raising / 10) if the pump has a max. 32m 
lifting H value should be about - 2.6. 

 

Setting the pressure switch - L 

 

1.

 

 Pressure off L1.2 or 1.5 should be adequate in most cases, if the pump starts when you turn on the tap, 
without having to change. 

2.

 

 if the pump does not start when you turn on the tap, increase the value of L to the launch of the pump. 

3.

 

 When the valve is closed the pump will stop, check the constant display np.2.2, then remove the faucet 
and check the displayed value prior to the start of the pump, np.1.2, then set L of 1.2 - 2.2, eg. 1.5 

 
 
3.

 

INSTALLATION 

1.

 

if you are using a circulating pump, install a valve in order to use the switch. 

Power 

max H 

pressure off  pressure switch 

128W 

25m 

H2.0 

L1.0 

250W 

32m 

H2.6 

L1.5 

370W 

35m 

H3.0 

L1.8 

550W 

40m 

H3.3 

L1.8 

750W 

55m 

H4.8 

L2.2 