INSTALLATION: 

 

Prior to any installation works, the power supply must always be disconnected. 
It also must be secured to prevent accidental reconnections. 

The pump can be connected after all the installation works are carried out on the 
pipework  which  will  form  a  part  of  the  installation  with  the  pump.  It  must  be 
remembered  that  welding  or  soldering  works  can  introduce  mechanical 
impurities into the pipework. The pipework should be flushed through, prior to 
the installation of the pump. 

The pump should be installed with its shaft in a horizontal position. The pump’s 
ports  can  be  in  different  positions  to  the  ones  shown  in  the  picture  below, 
however, the shaft of the pump must always be in a horizontal position. 
 

 

If  the  pump  is  installed  with  its  shaft  in  a  vertical  position,  the  bearings  may 
become  quickly  damaged  and  the  pump  may  fail.  This  type  of  equipment 
damage is not covered by the warranty and any repairs will have to be paid for. 

Summary of Contents for BETA 25-60

Page 1: ...s made by the user relating to the equipment s failure resulting from its inappropriate use CAUTION Non observance of recommendations listed in this operating manual may result in personal injuries or damage to units where the equipment is installed the environment or the pump itself CAUTION Children and persons with reduced physical sensory or mental capabilities must not use this equipment also ...

Page 2: ...igned to pump substances which are corrosive flammable or have damaging or explosive properties for example petrol nitro petroleum etc as well as foodstuffs and salt water Equipment failures caused by this type of damage are not covered by the product s warranty The maximum temperature of pumped water is 110o C The pump is not adapted to pump water with an excessive level of mineral particles as t...

Page 3: ... mechanical impurities into the pipework The pipework should be flushed through prior to the installation of the pump The pump should be installed with its shaft in a horizontal position The pump s ports can be in different positions to the ones shown in the picture below however the shaft of the pump must always be in a horizontal position If the pump is installed with its shaft in a vertical pos...

Page 4: ...CAL CONNECTION The pump s power supply network should satisfy the requirements listed on the rating plate The pump has a cable with a plug which can be inserted into an earthed socket The pump needs to be connected to a network with an active earthing system The manufacturer and the guarantor will bear no responsibility for injuries to people or any damage caused by the lack of an appropriate eart...

Page 5: ...d from the electrical network it should be unblocked failure repaired and switched on again Switching it off and then switching it back on again will reset the error message OPERATING MODE The subsequent pressing of the operating mode switch allows the user to select one of the eight settings The selected setting will be displayed by the operating mode display The pump s operating parameters are s...

Page 6: ...second parallel pipe is used to receive the cooled water from the radiators the most economic solution is to select the AUTO function This type of installation also permits the selection of a higher setting from PP1 alternating pressure 2 If a house has a one pipe heating system where the cooled water from a radiator enters a pipe supplying hot water to the next radiator and ...

Page 7: ...riod of approx 2 hours the pump will automatically start operating in night mode If the temperature of the heating medium increases by approx 10O C the pump will automatically return to the standard operating mode The night mode setting will not work if the pump is running in one of its constant speeds Disconnecting the electricity supply will deactivate the night mode Once the power supply is rec...

Page 8: ...he maximum temperature of the heating medium is 110O C With the ambient temperature of 40O C the maximum temperature of the heating medium is 70O C With the ambient temperature of 35O C the maximum temperature of the heating medium is 90O C Any equipment damage caused by water vapour condensation is not covered by a warranty The surface temperature of the pump must not exceed 120O C Any equipment ...

Page 9: ...eating medium to the installation The inlet pressure is too low Check the air quantity in the expansion vessel The pump is noisy there is noise in the installation The panel displays a number The pump performance is too high Decrease the pressure on the suction side The pump is running but provides insufficient heat The panel displays a number The pump operating parameters are too low Increase the...

Reviews: