48
Technical data
In order to protect the control panel and the pump stator against water steam condensation, always keep
the temperature of the heating medium higher than the ambient temperature.
Ambient temperature [°C]
Heating medium temperature [°C]
Minimum [°C]
Maxsimum [°C]
0
2
110
10
10
105
20
20
100
30
30
95
35
35
90
40
40
70
If the pump is used in the hot usable water system, it is recommended to reduce the water temperature below 65°C.
Power supply
1×230V +6%/-10%, 50Hz, PE
Motor protection
There is no need for additional motor protection
Protection rating
IP 44 for AMG, IP 42 for AMG SOLAR
Insulation class
E for AMG, F for AMG SOLAR
Maximum relative humidity
≤ 95%
Maximum pressure in the central heating system
1 MPa
Minimum inflow pressure at suction depending
on heating medium temperature
Medium temperature
Minimum inflow pressure
≤ 85°C
0.005 MPa
≤ 90°C
0.028 MPa
≤ 95°C
0.050 MPa
Acoustic pressure of working pump
"43 dB (A)
Permissible ambient temperature
0~+40°C
Maximum heating medium temperature
TF95 for AMG, TF110 for AMG SOLAR
Maximum heating up of pump surface
≤ 110°C
Range of temperatures of pumped liquid
2~+95°C for AMG, 2~+110°C for AMG SOLAR