1
Main
power
cable
If
possible,
ensure
that
the
two
uninterruptible
power
supplies
are
not
both
connected
to
the
same
power
source.
Attention:
Ensure
that
you
comply
with
the
following
requirements
for
uninterruptible
power
supplies:
v
Each
UPS
5125
should
be
connected
to
a
separate
branch
circuit.
v
A
UL
listed
15
A
circuit
breaker
must
be
installed
in
each
branch
circuit
that
supplies
power
to
the
UPS
5125.
v
The
voltage
supplied
to
the
UPS
5125
must
be
200
–
240
V
single
phase.
v
The
frequency
supplied
must
be
between
50
and
60
Hz.
Note:
If
the
UPS
5125
is
cascaded
from
another
UPS,
the
source
UPS
must
have
at
least
3
times
the
capacity
per
phase
and
the
total
harmonic
distortion
must
be
less
than
5%
with
any
single
harmonic
being
less
than
1%.
The
UPS
5125
should
also
have
input
voltage
capture
that
has
a
slew
rate
faster
than
3
Hz
per
second
and
1
msec
glitch
rejection.
10.
All
front
panel
indicators
of
the
UPS
5125
flash
for
a
short
time
while
the
UPS
5125
runs
a
self-test.
When
the
test
is
complete,
the
mode
indicator
1
flashes
to
show
that
the
UPS
5125
is
in
standby
mode.
See
Press
and
hold
the
UPS
5125
on
button
2
until
you
hear
the
UPS
5125
beep
(approximately
one
second).
The
mode
indicator
stops
flashing
and
the
load
level
indicators
display
the
percentage
of
load
that
is
being
supplied
by
the
UPS
5125.
The
UPS
5125
is
now
in
normal
mode,
and
is
charging
its
battery.
See
1
Mode
indicator
2
On
button
1
Figure
20.
Installing
the
uninterruptible
power
supply
power
cable
+ -
+ -
25%
100%
2
1
1
Figure
21.
Power
switch
and
indicators
on
the
uninterruptible
power
supply
5125
46
IBM
TotalStorage
SAN
Volume
Controller:
Installation
Guide
Summary of Contents for TotalStorage SAN Volume Controller
Page 1: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 2 1 0 SC26 7541 04...
Page 2: ......
Page 3: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 2 1 0 SC26 7541 04...
Page 8: ...vi IBM TotalStorage SAN Volume Controller Installation Guide...
Page 10: ...viii IBM TotalStorage SAN Volume Controller Installation Guide...
Page 11: ...Tables 1 Uninterruptible power supply support guidelines 17 Copyright IBM Corp 2003 2005 ix...
Page 12: ...x IBM TotalStorage SAN Volume Controller Installation Guide...
Page 30: ...xxviii IBM TotalStorage SAN Volume Controller Installation Guide...
Page 44: ...14 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 62: ...32 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 102: ...72 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 108: ...78 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 114: ...84 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 121: ......
Page 122: ...Part Number 64P8289 Printed in USA SC26 7541 04 1P P N 64P8289...
Page 123: ...Spine information IBM TotalStorage SAN Volume Controller Installation Guide Version 2 1 0...