on
a
metal
table.
Take
additional
care
when
handling
devices
during
cold
weather
because
heating
reduces
indoor
humidity
and
increases
static
electricity.
Heat
output,
airflow,
and
cooling
The
maximum
heat
output
of
the
DS4800
is
235
watts
(803.7
BTU/hr).
Each
DS4800
rack-mounted
unit
requires
an
airflow
of
2.5
m
3
(87
ft.
3
)
per
minute.
The
input
air
temperature
to
all
rack
cabinets
should
be
in
the
range
10°
C
-
35°
C
(50°
F
-
95°
F).
The
recommended
operating
temperature
is
22°
C
(72°
F).
When
rack
cabinets
that
contain
many
DS4800s
are
to
be
installed
together,
the
following
requirements
must
be
met
to
ensure
that
the
DS4800s
are
adequately
cooled:
v
Air
enters
at
the
front
of
the
rack
cabinet
and
leaves
at
the
back.
To
prevent
the
air
that
is
leaving
the
rack
cabinet
from
entering
the
intake
of
another
piece
of
equipment,
you
must
position
the
rack
cabinets
in
alternate
rows,
back-to-back
and
front-to-front.
This
arrangement
is
known
as
“cold
aisle/hot
aisle”
and
is
shown
in
v
Where
rack
cabinets
are
in
rows,
each
rack
cabinet
must
touch
the
rack
cabinet
that
is
next
to
it.
This
reduces
the
amount
of
hot
air
that
can
flow
around
from
the
back
of
the
rack
into
the
intakes
of
the
storage
subsystems
that
are
in
that
rack
cabinet.
You
should
use
Suite
Attach
Kits
to
completely
seal
any
gaps
that
remain
between
the
rack
cabinets.
For
details
about
Suite
Attach
Kits,
contact
your
marketing
representative.
v
Where
rack
cabinets
are
in
rows
front-to-front
or
back-to-back,
a
gap
of
at
least
1220
mm
(48
in.)
must
separate
the
rows
across
the
cold
aisle.
v
To
ensure
correct
airflow
in
each
rack
cabinet,
the
rack
filler
plates
must
be
installed
in
unused
positions.
Also,
all
the
gaps
in
the
front
of
the
rack
cabinets
must
be
sealed,
including
the
gaps
between
the
storage
subsystems.
28
IBM
System
Storage
DS4800
Storage
Subsystem:
Installation,
User’s,
and
Maintenance
Guide
Summary of Contents for TotalStorage DS4800
Page 2: ......
Page 18: ...xvi IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 22: ...xx IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 68: ...46 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 114: ...92 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 154: ...132 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 200: ...178 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 202: ...180 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 205: ...ds48021 Figure 102 DS4800 rear rack mounting template Appendix C Rack mounting templates 183...
Page 206: ...184 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 226: ...204 IBM System Storage DS4800 Storage Subsystem Installation User s and Maintenance Guide...
Page 233: ......
Page 234: ...Part Number 23R1992 Printed in USA GC26 7845 00 1P P N 23R1992...