Dimensions and weight
Ensure that space is available in a rack that is capable of supporting the node.
Table 9. Dimensions and weight
Height
Width
Depth
Maximum weight
4.3 cm
(1.7 in.)
44 cm
(17.3 in.)
73.7 cm
(29 in.)
15 kg
(33 lb)
Additional space requirements
Ensure that space is also available in the rack for the following additional space
requirements around the node.
Table 10. Additional space requirements
Location
Additional space
requirements
Reason
Left side and right side
Minimum: 50 mm (2 in.)
Cooling air flow
Back
Minimum: 100 mm (4 in.)
Cable exit
Maximum heat output of each SAN Volume Controller 2145-CG8
node
The node dissipates the following maximum heat output.
Table 11. Maximum heat output of each SAN Volume Controller 2145-CG8 node
Model
Heat output per node
SAN Volume Controller 2145-CG8
160 W (546 Btu per hour)
SAN Volume Controller 2145-CG8 plus
solid-state drives (SSDs)
210 W (717 Btu per hour)
Maximum heat output of each 2145 UPS-1U
The 2145 UPS-1U dissipates the following maximum heat output.
Table 12. Maximum heat output of each 2145 UPS-1U
Model
Heat output per node
Maximum heat output of 2145 UPS-1U
during normal operation
10 W (34 Btu per hour)
Maximum heat output of 2145 UPS-1U
during battery operation
100 W (341 Btu per hour)
Redundant ac-power environment requirements
Ensure that your physical site meets the installation requirements for the
redundant ac-power switch.
The redundant ac-power switch requires two independent power sources that are
provided through two rack-mounted power distribution units (PDUs). The PDUs
must have IEC320-C13 outlets.
Appendix B. SAN Volume Controller physical installation planning
49
Summary of Contents for SAN Volume Controller 2145-CG8
Page 6: ...vi SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 8: ...viii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 28: ...xxviii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 34: ...6 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 72: ...44 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 100: ...72 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 102: ...74 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 104: ...76 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 109: ......
Page 110: ...Part Number 31P1669 Printed in USA GC27 3923 02 1P P N 31P1669...