Note:
The optional SSDs and optional 10 Gbps Ethernet cannot be in the same
node.
Redundant ac-power switch
The redundant ac-power switch is an optional feature that makes the SAN Volume
Controller nodes resilient to the failure of a single power circuit. The redundant
ac-power switch is not a replacement for an uninterruptible power supply. You
must still use a uninterruptible power supply for each node.
You must connect the redundant ac-power switch to two independent power
circuits. One power circuit connects to the main power input port and the other
power circuit connects to the backup power-input port. If the main power to the
SAN Volume Controller node fails for any reason, the redundant ac-power switch
automatically uses the backup power source. When power is restored, the
redundant ac-power switch automatically changes back to using the main power
source.
Place the redundant ac-power switch in the same rack as the SAN Volume
Controller node. The redundant ac-power switch logically sits between the rack
power distribution unit and the 2145 UPS-1U.
You can use a single redundant ac-power switch to power one or two SAN Volume
Controller nodes. If you use the redundant ac-power switch to power two nodes,
the nodes must be in different I/O groups. In the event that the redundant
ac-power switch fails or requires maintenance, both nodes turn off. Because the
nodes are in two different I/O groups, the hosts do not lose access to the back-end
disk data.
For maximum resilience to failure, use one redundant ac-power switch to power
each SAN Volume Controller node.
Figure 1 shows a redundant ac-power switch.
Cabling of redundant ac-power switch (example)
You must properly cable the redundant ac-power switch units in your
environment.
Note:
While this topic provides an example of the cable connections, it does not
indicate a preferred physical location for the components.
svc00297
Figure 1. Photo of the redundant ac-power switch
2
SAN Volume Controller: Model 2145-CG8 Hardware Installation Guide
Summary of Contents for SAN Volume Controller 2145-CG8
Page 6: ...vi SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 8: ...viii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 28: ...xxviii SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 34: ...6 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 72: ...44 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 100: ...72 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 102: ...74 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 104: ...76 SAN Volume Controller Model 2145 CG8 Hardware Installation Guide...
Page 109: ......
Page 110: ...Part Number 31P1669 Printed in USA GC27 3923 02 1P P N 31P1669...