Table 85. Optimum operating ranges with power on
Measurement
Value
Temperature
16 - 32°C (60 - 90°F)
Relative humidity
40 - 50%
Powered off:
Plan for the required temperature and humidity ranges when the storage system is
off.
Table 86 provides the temperatures and humidity requirements for your storage
system when the power is off.
Table 86. Temperatures and humidity with the power off
Measurement
Value
Temperature
10 - 43°C (50 - 110°F)
Relative humidity
8 - 80%
Wet bulb temperature (maximum)
27°C (80°F)
In storage:
Plan for the required temperature and humidity ranges when the storage system is
in storage.
Table 87 provides the temperatures and humidity requirements for storing your
storage system.
Table 87. Temperatures and humidity while in storage
Measurement
Value
Temperature
1 - 60°C (34 - 140°F)
Relative humidity
5 - 80%
Wet bulb temperature (maximum)
29°C (84°F)
Corrosive gasses and particulates
Plan for air quality that meets standards for corrosive gases and particulates.
The storage system is designed to operate reliably in a general business-class
environment. A general business-class environment is one that has automated
24x7x365 temperature and humidity controls and also operates with G1
specifications for corrosive gases and P1 specifications for particulates.
Operating vibration and shock requirements
The vibration levels that are designed for the storage system comply with class V1
requirements included in the product classes for vibration.
The storage system is designed to operate under the vibration V1 levels that are
described in Table 88 on page 166. Additional information includes random
vibration PSD profile breakpoints and operational shock levels. See Table 89 on
page 166 and Table 90 on page 166.
Chapter 6. Delivery and installation requirements
165
Summary of Contents for DS8880 Series
Page 1: ...IBM DS8880 Version 8 Release 5 Introduction and Planning Guide GC27 8525 16 IBM...
Page 12: ...xii DS8880 Introduction and Planning Guide...
Page 52: ...40 DS8880 Introduction and Planning Guide...
Page 68: ...56 DS8880 Introduction and Planning Guide...
Page 138: ...126 DS8880 Introduction and Planning Guide...
Page 184: ...172 DS8880 Introduction and Planning Guide...
Page 190: ...178 DS8880 Introduction and Planning Guide...
Page 194: ...182 DS8880 Introduction and Planning Guide...
Page 200: ...188 DS8880 Introduction and Planning Guide...
Page 206: ...194 DS8880 Introduction and Planning Guide...
Page 208: ...196 DS8880 Introduction and Planning Guide...
Page 216: ...204 DS8880 Introduction and Planning Guide...
Page 220: ...208 DS8880 Introduction and Planning Guide...
Page 222: ...210 DS8880 Introduction and Planning Guide...
Page 243: ......
Page 244: ...IBM Printed in USA GC27 8525 16...