If your installation is not using a grounded-raised floor, and your servers are connected to an 9076 SP
Switch2 clustered environment, all attached server frames in your environment must be independently
grounded to the switch frame. Use the following information to help you install multiple systems to the
9076 SP Switch2 switch frame in a clustered environment:
v
Order grounding straps by calling the IBM Quality Hotline at 1-800-IBM-LINE and requesting Part
Number 44P3695, Grounding Kit. Each kit contains one ground strap and the required hardware to
make a single connection between a server and a 9076 SP Switch2, so order one kit for each server
that is connected to the switch.
v
An IBM service representative will install the grounding straps by using instructions that are provided
with the grounding kits. Each server frame must be directly connected to a 9076 SP Switch2 frame.
Eserver
pSeries 655 Physical Specifications and Loads
The following tables illustrate the physical, electrical and thermal, as well as acoustical and environmental
characteristics of various
Eserver
pSeries 655 system configurations.
Dimensions and Weight
Physical Characteristic
Slimline Doors
Acoustical Doors
Height
2028 mm (79.84 in.)
2028 mm (79.84 in.)
Width
785 mm (30.91 in.)
785 mm (30.91 in.)
Depth
1443 mm (56.81 in.)
1799 mm (70.83 in.)
Weight without IBF (max. config.)
1487 kg (3279 lbs.)
1496 kg (3299 lbs.)
Weight with IBF (max. config.)
1629 kg (3592 lbs.)
1638 kg (3612 lbs.)
Notes:
1. Doors are not installed during product shipment to the customer.
2. Refer to the following table for the approximate weight of your system configuration.
Approximate System Weights by Configuration
If the system that you order weighs more than 1134 kg (2500 lbs) when it is shipped from the factory, a
weight-distribution plate will be provided for the system. This plate is used to minimize the point loading
from casters and leveling pads.
Number of
Nodes, I/O
Drawers
Weight in kg (lbs)
Slim Doors
with IBF
Slim Doors
without IBF
Acoustic
Doors with
IBF
Acoustic
Doors without
IBF
No Doors with
IBF
No Doors
1, 0
616 (1359)
528 (1165)
625 (1379)
537 (1184)
590 (1301)
502 (1107)
2, 0
665 (1467)
577 (1273)
674 (1487)
586 (1292)
639 (1409)
551 (1215)
3, 0
740 (1631)
652 (1436)
749 (1651)
660 (1456)
714 (1573)
625 (1378)
4, 0
9016 (1986)
724 (1596)
910 (2005)
733 (1616)
875 (1928)
698 (1538)
5, 0
975 (2150)
798 (1760)
984 (2169)
807 (1780)
949 (2092)
772 (1702)
6, 0
1136 (2505)
871 (1920)
1145 (2524)
880 (1940)
1110 (2447)
845 (1862)
7, 0
1211 (2669)
945 (2084)
1219 (2688)
954 (2103)
1184 (2611)
919 (2026)
8, 0
1260 (2777)
994 (2192)
1268 (2796)
1003 (2211)
1233 (2719)
968 (2134)
9, 0
1334 (2941)
1069 (2356)
1343 (2960)
1077 (2375)
1308 (2883)
1042 (2298)
10, 0
1383 (3049)
1118 (2464)
1392 (3068)
1126 (2483)
1357 (2991)
1091 (2406)
11, 0
1457 (3212)
1192 (2628)
1466 (3232)
1201 (2647)
1431 (3154)
1166 (2570)
12, 0
1506 (3320)
1241 (2736)
1515 (3340)
1250 (2755)
1480 (3262)
1215 (2678)
94
Site and Hardware Planning Information
Summary of Contents for 7012 397
Page 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 2: ......
Page 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Page 11: ...Appendix Notices 385 Index 387 Contents ix...
Page 12: ...x Site and Hardware Planning Information...
Page 16: ...xiv Site and Hardware Planning Information...
Page 18: ...xvi Site and Hardware Planning Information...
Page 26: ...8 Site and Hardware Planning Information...
Page 238: ...220 Site and Hardware Planning Information...
Page 246: ...228 Site and Hardware Planning Information...
Page 284: ...266 Site and Hardware Planning Information...
Page 296: ...278 Site and Hardware Planning Information...
Page 366: ...348 Site and Hardware Planning Information...
Page 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Page 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Page 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Page 384: ...366 Site and Hardware Planning Information...
Page 402: ...384 Site and Hardware Planning Information...
Page 404: ...386 Site and Hardware Planning Information...
Page 413: ......
Page 414: ...Printed in USA SA38 0508 20...
Page 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...