Configuration
Only the available options are displayed.
User settings are not protected by default. You can enable the password through
the User Password setting.
The following table describes the options that you can change.
Table 8. Configuration settings
Description
Available settings
Default setting
Change language
[English] [French] [German] [Spanish] [Japanese] [Simplified
Chinese] [Russian] [Korean] [Traditional Chinese]
English
User password
[Enabled] [Disabled]
If Enabled, the default password is USER and cannot be
changed.
Note:
If you enter an incorrect password, the message
Wrong
Password
is displayed. Press any button to return to the password
screen and retry the password.
Disabled
Audible alarms
[Enabled] [Disabled]
Note:
If you disable audible alarms, it takes effect instantly and
remains disabled, even after a power cycle. This differs from the
mute feature, by which the horn is temporarily silenced when any
button is pressed but turns on again if a new alarm is triggered.
Enabled
Set date and time
Set Month, Day, Year, Hours, Minutes, and Seconds
Date: mm/dd/yyyy
01/01/2010
Time: hh:mm:ss
12:00:00
Notes:
1. The date format is dependent on the language selection.
2. Time is a 24-hour clock.
Control commands
from serial port
[Enabled] [Disabled]
If Enabled, control commands are accepted through the serial
port, USB ports, or option card.
If Disabled, configuration and load control commands are
restricted to LCD only.
Enabled
Output voltage
[Auto sensing]
[200V] [208V]
[220V] [230V] [240V]
Note:
Numerical output voltage settings that are configured in
Standby mode take effect immediately. Auto sensing and any
settings that are configured outside of Standby mode take effect
after the next power off and restart. Selecting auto sensing
disables the battery start feature until after the next successful
startup on utility power.
Auto sensing
Note:
The default auto
sensing runs once to set
the output voltage and
then is disabled.
Output frequency
[50Hz] [60Hz] [Auto sensing]
Note:
Numerical output frequency settings that are configured in
Standby mode take effect immediately. Auto sensing and any
settings that are configured outside of Standby mode take effect
after the next power off and restart. Selecting auto sensing
disables the battery start feature until after the next successful
startup on utility power.
Auto sensing
Note:
The default auto
sensing runs once to set
the output frequency and
then is disabled.
24
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
Summary of Contents for 6000 VA LCD 4U
Page 2: ......
Page 14: ...xii 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 32: ...18 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 70: ...56 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 74: ...60 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 82: ...68 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 6000 VA UPS and 6000 VA EBM Installation and Maintenance Guide...
Page 87: ......
Page 88: ...Part Number 81Y1032 Printed in USA 1P P N 81Y1032...