6. Connect the input and ground wires to the terminal block according to the
following illustration and Table 4.
Table 4. UPS wiring specifications
Wire functions
Terminal
position
UPS wire
function
Terminal wire
size rating
1
Tightening
torque
Input
1
Input ground
5.26 - 16 mm
2
(10-6 AWG)
2.49 Nm (22
inch-pounds)
2
L2 / Neutral In
3
L1 In
1
Use the following minimum wire size:
v
5.26 mm
²
(10 AWG) for equipment grounding wire, 75°C copper wire minimum
v
8.37 mm
²
(8 AWG) for input line and neutral wires, 75°C copper wire minimum
7. Replace the terminal block cover.
8. Continue to “UPS initial startup” on page 17.