![IBM 2810-A14 Manual Download Page 32](http://html1.mh-extra.com/html/ibm/2810-a14/2810-a14_manual_608714032.webp)
Table 9. Rack dimensions and clearances
Metric (mm)
English (in.)
General dimensions
Height
1991
78.4
Width
600
23.6
Depth
1142
45.0
Clearances
Front door
1200
47.2
Back door
1000
39.4
Service and cooling
See Figure 1 and Table 10 for detailed information.
Sides
You must adhere to the following space requirements around the sides of the
racks:
v
You must place racks no closer than 450 mm (17.7 in.) to a wall.
v
You can position racks alongside (adjacent to) other racks.
v
There are no space requirements between adjacent racks.
IBM service representatives must have enough space to open the front and rear
covers to service the unit, and must also be able to remove components and other
assemblies from the unit. See Figure 1 and Table 10 for minimum service
clearances.
Table 10. Clearance dimensions for service and cooling
Index
Metric (mm)
English (in.)
A
1200
47.2
Figure 1. Top view of clearance requirements for service and cooling
12
IBM XIV Storage System Introduction and Planning Guide
Summary of Contents for 2810-A14
Page 2: ......
Page 6: ...iv IBM XIV Storage System Introduction and Planning Guide...
Page 8: ...vi IBM XIV Storage System Introduction and Planning Guide...
Page 10: ...viii IBM XIV Storage System Introduction and Planning Guide...
Page 22: ...2 IBM XIV Storage System Introduction and Planning Guide...
Page 28: ...8 IBM XIV Storage System Introduction and Planning Guide...
Page 36: ...16 IBM XIV Storage System Introduction and Planning Guide...
Page 42: ...22 IBM XIV Storage System Introduction and Planning Guide...
Page 46: ...26 IBM XIV Storage System Introduction and Planning Guide...
Page 52: ...32 IBM XIV Storage System Introduction and Planning Guide...
Page 61: ......
Page 62: ...U S A GA52 1327 07...