IBM 2200VA LCD 2U Rack Uninterruptible Power Supply for IBM System x
6
Table 3. Specifications (continued)
Specification
IBM 2200VA LCD 2U Rack UPS
(100V/120V)
IBM 2200VA LCD 2U Rack UPS
(230V)
Communications and management
USB HID port
Yes
Yes
RS-232 serial port
Yes
Yes
Ethernet port
Optional using Network Management Card, 46M4110
Environmental Monitoring Probe
Optional Environmental Monitoring Probe, 46M4113
Management software included
IBM UPS Manager
Control panel
Intelligent three-button, dual color, backlit graphical LCD displays vital UPS
status in nine languages
Audible alarm
Alarm when on battery: Distinctive low-battery alarm
Remote Power Off (REPO)
REPO port
Surge Protection and Filtering
Surge energy rating
1200 Joules
2400 Joules
Filtering
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
The following tables list the expected period that the UPS will operate solely on batteries. Table 4 is for
the 100V/120V model and Table 5 is for the 230V model.
Table 4. IBM 2200VA UPS (100V/120V) runtime chart
Load
Run time on batteries
Load (%)
Load (VA)
Load (Watts)
Run time with standard
internal battery only
Run time with internal
battery plus External
Battery Module (EBM)
25%
500 VA
500 W
42 minutes
143 minutes
50%
969 VA
969 W
14 minutes
66 minutes
75%
1450 VA
1450 W
11 minutes
43 minutes
100%
1920 VA
1920 W
5 minutes
28 minutes
Table 5. IBM 2200VA UPS (230V) runtime chart
Load
Run time on batteries
Load (%)
Load (VA)
Load (Watts)
Run time with standard
internal battery only
Run time with internal
battery plus External
Battery Module (EBM)
25%
550 VA
500 W
41 minutes
138 minutes
50%
1100 VA
968 W
14 minutes
64 minutes
75%
1650 VA
1450 W
10 minutes
40 minutes
100%
2200 VA
1920 W
5 minutes
28 minutes