Table 8. Configuration settings (continued)
Description
Available settings
Default setting
Qualify bypass
[Always] [Never] [Bypass Disabled]
If
Always
is selected, the Bypass operation is allowed when:
v
Bypass voltages > the value set for Bypass Voltage Low Limit
v
Bypass voltages < the value set for Bypass Voltage High Limit
v
Bypass frequency > (nominal frequency -3 Hz)
v
Bypass frequency < (nominal fre3 Hz)
v
Inverter is synchronized with Bypass when unsynchronized
transfers are disabled by the value set for Unsynchronized
Transfers
If
Never
is selected, the Bypass operation is always allowed, if
the utility is within the UPS operating limits; voltage and
frequency limits are not in use. If
Bypass Disabled
is selected,
the Bypass operation is prohibited.
Always
Extended battery
modules (EBMs)
[0] [1]
See “Configuring the UPS for an extended battery module” on
page 40.
0
Battery low alarm
[Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm is triggered when the
set amount of backup time (approximately) remains in the
batteries.
3 minutes
Automatic battery tests [Enabled] [Disabled]
See “Running automatic battery tests” on page 41.
Enabled
Clear alarm history
The number after “Total events” shows how many events are
currently stored in the log. Press the OK button for 1 second to
reset the event count to zero and clear the log.
Not applicable
LCD contrast
[-5], [-4], [-3], [-2], [-1], [+0], [+1], [+2], [+3], [+4], [+5]
The display contrast is adjustable from -5 to +5. This range
covers the maximum adjustment for contrasting the background
with the text in the visual display of the control panel.
[+0]
REPO input polarity
[Open] [Closed]
If
Open
is selected, the normally open contacts activate the
alarm when the contacts close. If
Closed
is selected, the
normally closed contacts activate the alarm when the contacts
open.
Open
34
11000 VA UPS and 11000 VA EBM: Installation and Maintenance Guide
Summary of Contents for 11000 VA LCD 5U
Page 2: ......
Page 13: ...Taiwan Class A compliance statement 71 Index 73 Contents xi...
Page 14: ...xii 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 40: ...26 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 56: ...42 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 60: ...46 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 76: ...62 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 86: ...72 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 90: ...76 11000 VA UPS and 11000 VA EBM Installation and Maintenance Guide...
Page 91: ......
Page 92: ...Part Number 60Y1454 Printed in USA 1P P N 60Y1454...