8.2.3 Low Water Cut-off error
Low Water Cutoff Error
Issue
Diagnosis
Fix
Error - Low Water Cutoff
The Safety and Ignition
module has detected a low
water condition.
Refer to the
V10 Touchscreen
Controller
manual for
information on resetting a
boiler after a LWCO lockout.
8.2.4 Aux. Interlock 1 or 2
Aux. Interlock 1 or 2
Issue
Diagnosis
Fix
Interlock 1 or 2 terminals are
open.
Jumper lead is loose or
compromised.
Replace the jumper lead.
External safety is in an alarm
state.
Inspect the external safety
devices.
8.3 Miscellaneous touchscreen controller errors
Miscellaneous errors
Issue
Diagnosis
Fix
“ Loop/Indoor Sensor”
“Insufficient Air Flow”
“Insufficient Water Pressure”
The sensor
plug is not
engaged.
Check the P501 plug is
fully engaged in the back
of the controller board.
“Unknown Error”
The sensor
plug is not
engaged.
Check the P501 plug is
fully engaged in the back
of the controller board.
Temperature
sensor input
problem.
Test each temperature
sensor for appropriate
readings and Replace
defective temperature
sensor.
98
Section: Troubleshooting
Summary of Contents for SL Series
Page 8: ...Intentionally left empty...
Page 12: ...Figure 5 Top view SL 40 399 G3 Figure 6 Bottom view SL 40 399 G3 8 Section Specifications...
Page 14: ...Intentionally left empty...
Page 64: ...Figure 40 Electric wiring connections 60 Section Installation...
Page 76: ...Intentionally left empty...
Page 96: ...Intentionally left empty...
Page 108: ...Intentionally left empty...
Page 110: ...Internal wiring diagram Figure 46 Internal wiring diagram 106 Section Appendices...
Page 111: ...Sequence of operations Figure 47 Sequence of Operation 107 Sequence of operations...