Shutoff valve
Figure 43
Gas valve and fan components - EX 700, 850
The High Fire (gas-air ratio) adjustment screw will have to be adjusted to attain optimum
combustion results whenever fuel conversion is undertaken, however, no mixture adjustment shall
be performed unless done by a qualified technician using properly functioning and calibrated
combustion analyzing equipment.
1. Ensure you are installing the correct fuel conversion kit for your boiler. Compare the boiler
model number with the Kit # found in
.
2. Carefully follow the procedures of the fuel conversion instructions on:
a. Fuel Conversion
b. Combustion Testing and Adjustment
c. Placing conversion labels associated with the new fuel onto the boiler.
Fuel conversion kit part numbers
Model Number
Natural Gas to Propane
Propane to Natural Gas
EX 400
P-1236
P-1235
EX 500
P-1238
P-1237
EX 700
P-1201
P-1200
EX 850
P-1203
P-1202
Table 10
Fuel Conversion Kits
6.3.2.1 Performing a fuel conversion on EX 400 and EX 500 appliances
The following steps document replacing the current orifice with the kit-supplied orifice. After
replacing the orifice, you will need to tune the gas valve.
1. Disconnect the power to the boiler, and close the gas shut-off valve.
2. Remove the front door and top cover from the boiler.
3. Remove the bolts of the elbow (mixer side) marked
j
(see image below).
4. Remove the bolts of the elbow (gas valve side) marked
k
(see image below).
69
6.3.2 Performing a fuel conversion
Summary of Contents for EX Series
Page 62: ...Intentionally left empty...
Page 80: ...Intentionally left empty...
Page 121: ...Appendices Wiring diagrams Figure 73 Controller electrical diagram 119 Appendices...
Page 122: ...Figure 74 Internal wiring diagram EX 400 and EX 500 models 120 Section Appendices...
Page 123: ...Figure 75 Internal wiring diagram EX 700 and EX 850 models 121 Wiring diagrams...
Page 124: ...Figure 76 Sequence of Operation 122 Section Appendices...
Page 126: ...Intentionally left empty...
Page 128: ...126 Boiler parts diagram EX 400 and EX 500...