USER’S INFORMATION MANUAL

14

DC/HC SERIES BOILERS

Relief Valve - Maintenance and Testing

The relief valve manufacturer requires that under normal operating conditions 

a “try lever test” must be performed every two months. Under severe service 

conditions, or if corrosion and/or deposits are noticed within the valve body, 

testing must be performed more often. A “try lever test” must also be performed 

at the end of any non-service period.
Test at or near maximum operating pressure by holding the test lever fully open 

for at least 5 seconds to flush the valve seat free of sediment and debris. Then 

release the lever and permit the valve to snap shut.
If the lever does not activate, or there is not evidence of discharge, discontinue 

use of equipment immediately and contact a licensed contractor or qualified 

service personnel.
If the relief valve does not completely seal, and fluid continues to leak from the 

discharge pipe - perform the test again to try and flush any debris that may be 

lodged in the valve. If repeated tries fail to stop the leakage, contact a licensed 

contractor or qualified service personnel to replace the valve.
While performing a “try lever test”, a quantity of heat transfer fluid will be 

discharged from the piping system and the system pressure will drop. This fluid 

must be replaced. It is highly recommended that a system pressurization unit, 

such as an 

Axiom Industries model MF200

 be employed to refill and pressurize 

your system. Capture the discharged fluid in a container and recycle it by 

returning it to the system feeder unit. This is particularly important when your 

system contains treatment chemicals or glycol solutions. If the system employs 

plain water, the boiler auto fill valve must be turned on in order to recharge the 

lost fluid.

Domestic Hot Water System

Quality of the domestic cold water is very important to the longevity of the boiler. 

The recommended pH of the domestic water is between 6.5 and 8.5. The internal 

domestic water heat exchanger tubing and the flow sensor is subject to fouling if 

exposed to hard water (over 7 grains of hardness) or has a TDS of 500mg/L or 

higher.

 See Table 5.

DESCRIPTION

MAX

MIN

Water Pressure

150 psi

40 psi

Programmable water temperature

149°F (65°C)

104°F (40°C)

Minimum Flow Rate to Activate DHW Sensor

N/A

0.5 GPM

Acceptable pH range

7.5 pH

6.5 pH

Chloride

250 mg/L

Iron

0.3mg/L

Total Dissolved Solids

500mg/L

Total Hardness

7 grains

Table 5: Domestic Water Quality Guidelines

CAUTION

Before testing the relief valve, 

make certain the discharge 

pipe is properly connected to 

the valve outlet and arranged 

to contain and safely dispose 

of equipment discharge.

NOTE

Installers should inquire of 

local water purveyors as to 

the suitability of their supply 

for use in hydronic heating 

systems.
If water quality is questionable, 

a local water treatment expert 

must be consulted for testing, 

assessment and, if required, 

treatment.
Alternatively, water or hydronic 

fluid of known quality can be 

brought to the site.

WARNING

Do not use automotive-type 

ethylene or other types of 

automotive glycol antifreeze, 

or undiluted antifreeze of 

any kind. This may result 

in severe boiler damage. It 

is the responsibility of the 

Installer to ensure that glycol 

solutions are formulated to 

inhibit corrosion in hydronic 

heating systems of mixed 

materials. Improper mixtures 

and chemical additives may 

cause damage to ferrous and 

non-ferrous components as 

well as non-metallic, wetted 

components, normally found 

in hydronic systems. Ethylene 

glycol is toxic, and may be 

prohibited for use by codes 

applicable to your installation 

location. For environmental 

and toxicity reasons, IBC 

recommends only using non-

toxic propylene glycol.

Summary of Contents for DC Series

Page 1: ...ble materials in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Imme...

Page 2: ...he information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Points out a potentially hazardous situation which...

Page 3: ...HC SERIES BOILERS CONTROL 8 USER INSTALLER INTERFACE 8 TANKLESS DOMESTIC HOT WATER MODES 10 OPERATING AND SERVICE DISPLAY CODES 11 LIGHTING AND SHUTTING DOWN THE BOILER 12 MAINTENANCE 13 PARTS DIAGRAM...

Page 4: ...USER S INFORMATION MANUAL 4 DC HC SERIES BOILERS PAGE INTENTIONALLY LEFT BLANK...

Page 5: ...in 6 152mm of the DHW HOT outlet connection with the relief valve spindle installed in the vertical position The water heater if utilized requires a pressure relief valve identi ed with the ASME V or...

Page 6: ...limits are as follows Acidity pH is to be between 6 5 and 8 5 Chloride is to be less than 125 mg l Iron is to be less than 0 3 mg l Cu less than 0 1 mg l Conductivity is to be less than 400 S cm at 2...

Page 7: ...next to outdoor pools and spas WARNING The boiler shall not be exposed to water leaks from piping or components located overhead This includes condensation dropping from un insulated cold water lines...

Page 8: ...nclude upper and lower case letter and a combination with a period after the letter Example C c c are all valid parameter codes When adjusting settings double check that you are in the correct paramet...

Page 9: ...he Domestic Hot Water Temperature Press the Space Heating DHW Toggle button a second time and the LED beside the will illuminate and the current tankless domestic hot water temperature target is displ...

Page 10: ...re set in parameter n or as set for the Tankless hot water temperature This is the least efficient mode but does offer the most consistent hot water delivery temperatures This temperature will be the...

Page 11: ...ost purge XXX 1 Boiler water temperature reached target boiler pump is energized call for heat still present XXX 2 Self test When power is applied to the boiler the controller enters a self diagnostic...

Page 12: ...USER S INFORMATION MANUAL 12 DC HC SERIES BOILERS LIGHTING AND SHUTTING DOWN THE BOILER...

Page 13: ...qualified service technician as soon as possible for service Check the condensate trap and outlet pipe The condensate trap shall be full of water The outlet hose may be connected to a condensate neutr...

Page 14: ...to recharge the lost fluid Domestic Hot Water System Quality of the domestic cold water is very important to the longevity of the boiler The recommended pH of the domestic water is between 6 5 and 8...

Page 15: ...15 USER S INFORMATION MANUAL DC HC SERIES BOILERS PAGE INTENTIONALLY LEFT BLANK...

Page 16: ...USER S INFORMATION MANUAL 16 DC HC SERIES BOILERS PARTS DIAGRAMS DC Series Modulating Boiler Parts assembly Diagram 1 Boiler assembly parts...

Page 17: ...R S INFORMATION MANUAL DC HC SERIES BOILERS Diagram 2 Boiler assembly parts list refer to Diagram 6 1 1 on opposite page Some parts are available in Kits Please visit www ibcboiler com for more inform...

Page 18: ...USER S INFORMATION MANUAL 18 DC HC SERIES BOILERS HC Series Modulating Boiler Parts assembly Diagram 3 Boiler assembly parts...

Page 19: ...SER S INFORMATION MANUAL DC HC SERIES BOILERS Diagram 4 Boiler assembly parts list refer to Diagram 3 on opposite page Some parts are available in Kits Please visit www ibcboiler com for more informat...

Page 20: ...USER S INFORMATION MANUAL 20 DC HC SERIES BOILERS SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Page 21: ...21 USER S INFORMATION MANUAL DC HC SERIES BOILERS NOTES...

Page 22: ...DE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases Th...

Page 23: ...FORMATION MANUAL DC HC SERIES BOILERS REVISION HISTORY R1 JULY 2014 Initial release R2 SEPTEMBER 2014 Addition of the HC 13 50 R3 AUGUST 2015 Address Update R4 OCTOBER 2015 Addition of the DC 20 125 a...

Page 24: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 184 A R4 88534704 October 2015 IBC Technologies Inc 2015...

Reviews: